[Alarm information]
Each message in the table is displayed to give a warning but does not cause the inverter to trip.
Error code
/
/
Note)
When the ON/OFF function is selected for DC braking (DB), using the input terminal selection parameter, you can judge
the inverter to be normal if "" disappears when opening the circuit between the terminal and CC.
[Prealarm display]
Overcurrent alarm
Overvoltage alarm
Overload alarm
Overheat alarm
Problem
• The ST-CC circuit is opened.
ST terminal OFF
Undervoltage in main
• The supply voltage between R, S and T is
circuit
under voltage.
Retry in process
• The inverter is n the process of retry.
• A momentary stop occurred.
Frequency point
• The frequency setting signals at points 1
setting error alarm
and 2 are set too close to each other.
Clear command
• This message is displayed when pressing
acceptable
the STOP key while an error code is
displayed.
Emergency stop
• The operation panel is used to stop the
command acceptable
operation in automatic control or remote
control mode.
Setting error alarm /
• An error is found in a setting when data is
An error code and
reading or writing.
data are displayed
alternately twice
each.
Display of first/last
• The first and last data item in the
data items
data group is displayed.
• DC braking in process
DC braking
Shaft fixing control
• Motor shaft fixing control is in process.
Flowing out of
• The number of digits such as frequencies
excess number of
is more than 4.
digits
(The upper digits have a priority.)
Momentary power
• The slowdown stop prohibition function
failure slowdown
set with (momentary power
stop prohibition
failure ride-through operation) is
function activated.
activated.
Auto-stop because of
• The automatic stop function selected with
continuous operation
was activated.
at the lower-limit
frequency
Parameters in the
• Parameters are being initialized to default
process of
values.
initialization
Operation panel key
• The same key is held down for more than
fault
20 seconds.
• Some key is faulty.
Auto-tuning
• Auto-tuning in process
Same as (overcurrent)
Same as (overvoltage)
Same as and (overload)
Same as (overheat)
Possible causes
• Close the ST-CC circuit.
• Measure the main circuit supply voltage.
• The inverter is normal if it restarts after
• Set the frequency setting signals at points
• Press the STOP key again to clear the
• Press the STOP key for an emergency
• Check whether the setting is made
• Press MODE key to exit the data group.
• The message goes off in several tens of
• Normal if the message disappears when
• Lower the frequency free unit
• To restart operation, reset the inverter or
• To deactivate the automatic stop function,
• Normal if the message disappears after a
• Check the operation panel.
• Normal if it the message disappears after
85
E6581160
Remedies
If the voltage is at a normal level, the
inverter requires repairing.
several tens of senconds.
The inverter restarts automatically. Be
careful of the machine because it may
suddenly restart.
1 and 2 apart from each other.
trip.
stop.
To cancel the emergency stop, press any
other key.
correctly.
seconds if no problem occurs. Note)
a stop command is entered (or the
operation command is canceled).
magnification .
input an operation signal again.
increase the frequency command above
the lower-limit frequency (LL) + 0.2 Hz or
turn off the operation command.
while (several seconds to several tens of
seconds).
a few seconds.