Propane Gas Tanks And Piping; Circulating Air & Filters; Uctwork Ir Low - Goodman GMH95 Installation Instructions Manual

Gmh95/gch95/gme95/gch9 series gas-fired warm air furnace
Hide thumbs Also See for GMH95:
Table of Contents

Advertisement

G
P
C
AS
IPING
HECKS
Before placing unit in operation, leak test the unit and gas connec-
tions.
T
O AVOID THE POSSIBILITY OF EXPLOSION OR FIRE
MATCH OR OPEN FLAME TO TEST FOR LEAKS
Check for leaks using an approved chloride-free soap and water
solution, an electronic combustible gas detector, or other approved
testing methods.
NOTE: Never exceed specified pressures for testing. Higher
pressure may damage the gas valve and cause subsequent
overfiring, resulting in heat exchanger failure.
Disconnect this unit and shutoff valve from the gas supply piping
system before pressure testing the supply piping system with pres-
sures in excess of 1/2 psig (3.48 kPa).
Isolate this unit from the gas supply piping system by closing its
external manual gas shutoff valve before pressure testing supply
piping system with test pressures equal to or less than 1/2 psig
(3.48 kPa).
P
G
T
ROPANE
AS
ANKS AND
I
F THE GAS FURNACE IS INSTALLED IN A BASEMENT
AREA OR A CONFINED SPACE
CONTACT A PROPANE SUPPLIER TO INSTALL A GAS DETECTING
WARNING DEVICE IN CASE OF A GAS LEAK
• S
INCE PROPANE GAS IS HEAVIER THAN AIR
SETTLE IN ANY LOW AREAS OR CONFINED SPACES
• P
ROPANE GAS ODORANT MAY FADE
U
NDETECTABLE EXCEPT FOR WITH A WARNING DEVICE
A gas detecting warning system is the only reliable way to detect a
propane gas leak. Rust can reduce the level of odorant in propane
gas. Do not rely on your sense of smell. Contact a local propane
gas supplier about installing a gas detecting warning system. If
the presence of gas is suspected, follow the instructions on Page
4 of this manual.
All propane gas equipment must conform to the safety standards
of the National Board of Fire Underwriters, NBFU Manual 58.
For satisfactory operation, propane gas pressure must be 11 inch
w.c. at the furnace manifold with all gas appliances in operation.
Maintaining proper gas pressure depends on three main factors:
1. Vaporization rate, depending on temperature of the liquid,
and "wetted surface" area of the container or containers.
2. Proper pressure regulation. (Two-stage regulation is
recommended for both cost and efficiency).
3. Pressure drop in lines between regulators, and between
second stage regulator and the appliance. Pipe size will
depend on length of pipe run and total load of all appliances.
Complete information regarding tank sizing for vaporization, rec-
ommended regulator settings, and pipe sizing is available from
most regulator manufacturers and propane gas suppliers.
Since propane gas will quickly dissolve white lead and most stan-
dard commercial compounds, special pipe dope must be used.
Shellac-based compounds resistant to the actions of liquefied
petroleum gases such as Gasolac
®
Crane
are satisfactory.
Refer to the following illustration for typical propane gas installa-
tions.
WARNING
,
NEVER USE A
.
P
IPING
WARNING
,
AN EXCAVATED
,
IT IS STRONGLY RECOMMENDED TO
.
,
ANY LEAKING AS CAN
.
,
MAKING THE GAS
.
®
, Stalactic
®
, Clyde's
Sizing Between First and Second Stage Regulator*
Maximum Propane Capacities listed are based on 2 psig pressure drop at 10 psig setting.
Capacities in 1,000 BTU/hour.
Pipe or
Tubing
Length,
3/8"
Feet
10
730
20
500
30
400
40
370
50
330
60
300
80
260
100
220
125
200
150
190
175
170
200
160
To convert to capacities at 15 psig settings - multiply by 1.130
To convert to capacities at 5 psig settings - multiply by 0.879
Sizing Between Single or Second Stage Regulator and Appliance*
Maximum Propane Capacities Listed are Based on 1/2" W.C. pressure drop at 11" W.C. setting.
Capacities in 1,000 BTU/hour.
Pipe or
Tubing
Length,
3/8"
1/2"
Feet
10
39
20
26
30
21
40
19
50
18
60
16
80
13
100
11
125
10
150
9
200
8
250
8
*Data in accordance with NFPA pamphlet NO. 54
D
- A
UCTWORK
N
EVER ALLOW THE PRODUCTS OF COMBUSTION
M
,
ONOXIDE
TO ENTER THE RETURN DUCT WORK OR CIRCULATION
A
.
IR SUPPLY
Duct systems and register sizes must be properly designed for the
CFM and external static pressure rating of the furnace. Design the
ductwork in accordance with the recommended methods of "Air
Conditioning Contractors of America" Manual D.
Install the duct system in accordance with Standards of the Na-
tional Board of Fire Underwriters for the Installation of Air Condi-
tioning, Warm Air Heating and Ventilating Systems. Pamphlets No.
®
or John
90A and 90B.
31
5 to 15 PSIG
First Stage
(20 PSIG Max.)
Regulator
200 PSIG
Second Stage
Maximum
Regulator
Propane Gas Installation (Typ.)
Tubing Size, O.D. Type L
1/2"
5/8"
3/4"
1,700
3,200
5,300
1,100
2,200
3,700
920
2,000
2,900
850
1,700
2,700
770
1,500
2,400
700
1,300
2,200
610
1,200
1,900
540
1,000
1,700
490
900
1,400
430
830
1,300
400
780
1,200
380
730
1,100
Propane Gas Piping Chart I
Tubing Size, O.D. Type L
5/8"
3/4"
7/8"
1-1/8"
1/2"
92
199
329
501
935
275
62
131
216
346
630
189
50
107
181
277
500
152
41
90
145
233
427
129
37
79
131
198
376
114
35
72
121
187
340
103
29
62
104
155
289
89
26
55
90
138
255
78
24
48
81
122
224
69
21
43
72
109
202
63
19
39
66
100
187
54
17
36
60
93
172
48
Propane Gas Piping Chart II
XIII. CIRCULATING AIR & FILTERS
F
IR
LOW
WARNING
Continuous
11" W.C.
Nominal Pipe Size
Schedule 40
7/8"
1/2"
3/4"
8,300
3,200
7,500
5,800
2,200
4,200
4,700
1,800
4,000
4,100
1,600
3,700
3,700
1,500
3,400
3,300
1,300
3,100
2,900
1,200
2,600
2,600
1,000
2,300
2,300
900
2,100
2,100
830
1,900
1,900
770
1,700
1,800
720
1,500
Nominal Pipe Size
Schedule 40
3/4"
1"
1-1/4" 1-1/2"
567
1,071
2,205
3,307
393
732
1,496
2,299
315
590
1,212
1,858
267
504
1,039
1,559
237
448
913
1,417
217
409
834
1,275
185
346
724
1,066
162
307
630
976
146
275
567
866
132
252
511
787
112
209
439
665
100
185
390
590
,
INCLUDING CARBON

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents