Unit Inspection - Trane YSC060 Installation Operation & Maintenance

Packaged gas/electric
Table of Contents

Advertisement

Zone Sensor (BAYSENS010B)
This electronic sensor features four sys-
tem switch settings (Heat, Cool, Auto,
and Off) and two fan settings (On and
Auto) with four system status LED's. It is
a manual or auto changeover control with
dual setpoint capability. It can be used
with a remote zone temperature sensor
BAYSENS017B.
Programmable Zone Sensor -
(BAYSENS019B)
This 7 day programmable sensor fea-
tures 2, 3 or 4 periods for Occupied or
Unoccupied programming per day. If
the power is interrupted, the program is
retained in permanent memory. If power
is off for an extended period of time,
only the clock and day may have to be
reset.
The Zone Sensor allows selection of 2,
3 or 4 system modes (Heat, Cool, Auto,
and Off), two fan modes (On and Auto).
It has dual temperature selection with
programmable start time capability.
The occupied cooling set point ranges
between 45 F (7.2 C)and 98 F (35.6 C)
degrees. The heating set point ranges
between 43 F (6.1 C) and 96 F ( 35.6
C) degrees.
A liquid crystal display (LCD) displays
zone temperature, temperature set
points, day of the week, time, and op-
erational mode symbols.
The Option Menu is used to enable or
disable applicable functions, i.e.; Morn-
ing Warm-up, Economizer minimum po-
sition override during unoccupied sta-
tus, Fahrenheit or Centigrade, Supply
air tempering, Remote zone tempera-
ture sensor, 12/24 hour time display,
Smart fan, and Computed recovery.
During an occupied period, an auxiliary
relay rated for 1.25 amps @ 30 volts
RT-SVX31A-EN
General Information
AC with one set of single pole double
throw contacts is activated.
Status Inputs (4 Wires Optional)
The ZSM can be wired to receive four
(4) operating status
signals from the RTRM (HEAT, COOL,
SYSTEM "ON", SER-VICE).
Four (4) wires from the RTRM should be
connected to
the appropriate terminals (7, 8, 9 & 10)
on the ZSM.
Remote Zone Sensor
(BAYSENS013B)
This electronic sensor features remote
zone sensing and timed override with
override cancellation. It is used with a
TM
Trane Integrated Comfort
management system.
Remote Zone Sensor
(BAYSENS014B)
This electronic sensor features single
setpoint capability and timed override
with override cancellation. It is used
with a Trane Integrated Comfort
ing management system.
Remote Zone Sensor
(BAYSENS016A)
This bullet type temperature sensor can
be used for; outside air (ambient) sens-
ing, return air temperature sensing,
supply air temperature sensing, remote
temperature sensing (uncovered. Wir-
ing procedures vary according to the
particular application and equipment in-
volved. Refer to the unit's wiring dia-
grams for proper connections.
Remote Zone Sensor
(BAYSENS017B)
This electronic sensor can be used with
BAYSENS006B, 008B, 010B, 019B Re-
mote Panels. When this sensor is wired
to a BAYSENS019B Remote Panel,
wiring must be 18 AWG (.75mm
Shielded Twisted Pair (Belden 8760 or
equivalent). Refer to The specific Re-
mote Panel for wiring details.
BAYSTAT036A
Single Stage - 1 Heat/1 Cool
BAYSTAT037A
Multi Stage - 2 Heat/2 Cool - Can be
Used for Economizer Operation
BAYSENS025A
Remote sensor for BAYSTAT036A and
BAYSTAT037A
Phase Monitor (Optional)
ReliaTel Control Only
This sensor monitors voltage between
the 3 conductors of the 3 phase power
supply. Two LED lights are provided.
building
The green light indicates that a bal-
anced 3 phase supply circuit is prop-
erly connected. The red light indicates
that unit operation has been pre-
vented. There are two conditions that
will prevent unit operation.The power
supply circuit is not balanced with the
proper phase sequence of L1,L2,L3 for
TM
build-
the 3 conductors of a 3 phase circuit.
The line to line voltage is not between
180 volts and 633 volts.