Installation - Harman P61A Installation & Operating Manual

Freestanding pellet stove
Table of Contents

Advertisement

R eq uirements for Terminating the V enting
WARNING: enting terminals must not be recessed into a
wall or siding.
NOTE: Only approved pellet vent pipe, wall pass-throughs,
and fire stops should be used when venting through
combustible materials.
NOTE: Always take into consideration the effects of the
prevailing wind direction or other wind currents that may
cause flyash and or smoke when placing the termination of
the vent.
In addition, the following must be observed:
A. The clearance above grade must be a minimum of 12 .
B. The clearance to a window or door that may be opened
must be a minimum of 8 to the side, 8 below the
window door, and 12 above the window door. (with
outside air installed, 1 8 " to the side or below)
C. A 12 clearance to a permanently closed window is
recommended to prevent condensation on the window.
. The vertical clearance to a ventilated soffit located above
the terminal within a horizontal distance of 2 feet ( 0 cm)
from the center-line of the terminal must be a minimum
of 18 .
E. The clearance to an unventilated soffit must be a minimum
of 12 .
. The clearance to an outside corner is 11 from center of
pipe.
G. The clearance to an inside corner is 12 .
Sidewalk
V
7
P 6 1 A P ellet S tove
Inside Corner
Detail
Fixed
Closed
Openable
=Vent Terminal
V enting
H. A vent must not be installed within
a gas meter regulator assembly when measured from the
horizontal center-line of the regulator.
I. The clearance to service regulator vent outlet must be a
minimum of
. The clearance to a non-mechanical air supply inlet to the
building or the combustion air inlet to any other appliance
must be a minimum of 8 .
. The clearance to a mechanical air supply inlet must be a
minimum of 10 feet. (with outside air installed, 6 feet )
L. The clearance above a paved sidewalk or a paved
driveway located on public property must be a minimum
of 7 feet.
. The clearance under a veranda, porch, deck or balcony
must be a minimum of 12 inches. (B. also applies)
NOTE: The clearance to vegetation and other exterior
combustibles such as mulch is
center of the outlet or cap. This
or a minimum of 7 feet below the outlet.
Certain Canadian and or Local codes or regulations may
require different clearances.
A vent shall not terminate directly above a side-walk or
paved driveway which is located between two single family
dwellings and serves both dwellings.
Only permitted if veranda, porch, deck, or balcony is fully
open on a minimum of 2 sides beneath the floor.
NOTE: W here passage through a wall, or partition of
combustible construction is desired, the installation
shall conform to CAN/ CSA-B3 6 5 . (if in Canada)
Openable
Fixed
Closed
A
=Air Supply Inlet
feet ( 0 cm) above
feet.
as measured from the
radius continues to grade
Porch or
Openable
=Area where termination is mot permitted
3 -9 0 -0 5 8 2 2 R 2 8 _ 0 8 /1 3
Deck
or Fixed