Hot Water Coil Heating Capacities - York LEU360 Technical Manual

Split-system air-cooled evaporator blower 30, 40 & 50 ton
Table of Contents

Advertisement

550.13-TG2Y (799)
TABLE 4: 2LP* MOTOR OVERLOAD ELEMENTS
VOLTAGE
MOTOR HP
200 V
OLTS
230 V
10 HP Motor
OLTS
460 V
OLTS
200 V
OLTS
230 V
15 HP Motor
OLTS
460 V
OLTS
TABLE 5: 2LP* MOTOR STARTERS
MOTOR HP @ VOLTAGE
10HP motor @ 200 volts
or
15 HP motor @ 200 or 230 volts
10HP motor @ 230 or 460 volts
or
15 HP motor @ 460 volts
TABLE 6: HOT WATER COIL HEATING CAPACITIES
HOT WATER
UNIT
COIL MODEL
MODEL
1HW0406
LEU360
LEU480
1HW0407
LEU600
1.
These capacities do not include any blower motor heat.
NOTE: Temperature Water Drop (°F) = (2 x MBH)/GPM
6
KIT #
2MP04701600
2MP04701400
2MP04701300
2MP04701500
2MP04701700
2MP04701200
KIT NUMBER
2MS04700100
(60 AMP)
2MS04700200
(30 AMP)
ENTERING WATER TEMPERATURE MINUS ENTRY AIR TEMPERATURE, °F.
GPM
CFM
70
8,000
236
10,000
265
50
12,000
291
14,000
315
12,800
348
75
16,000
389
19,200
425
16,000
389
75
20,000
436
24,000
473
DO NOT OPERATE THE SUPPLY AIR BLOWER
MOTOR ABOVE ITS NOMINAL HP RATING
WHEN A UNIT IS EQUIPPED WITH A HOT
WATER COIL ACCESSORY. DO NOT USE
STEAM IN HOT WATER Coils.
DO NOT OPERATE THE SUPPLY AIR BLOWER
ABOVE ITS NOMINAL HP RATING WHEN A
UNIT IS EQUIPPED WITH A STEAM COIL
ACCESSORY.
ALTHOUGH THESE COILS ARE SUITABLE OF
A MUCH HIGHER PRESSURE, STEAM ABOVE
25 PSIG PROVIDES TOO MUCH HEAT THAT
COULD DAMAGE THE BLOWER MOTOR.
1
.
90
110
304
372
341
416
374
457
405
495
447
547
500
611
547
668
500
611
561
686
610
746
130
150
440
508
492
568
540
623
585
675
646
746
722
833
790
911
722
833
810
935
882
1,019
Unitary Products Group

Advertisement

Table of Contents
loading

This manual is also suitable for:

Leu480Leu600

Table of Contents