® PROVEN PERFORMANCE GENERAL The LA/LB line is a flexible performer. LA300, LB360 & 480 can be positioned in up to 12 different positions and sus- pended in various positions. The LB600 can be positioned in up to 7 different arrangements and suspended also. The LA/...
036-21335-002-A-1102 YORK SPLIT INDOOR PRODUCT NOMENCLATURE Model Number Model # Description Product Category Product Identifier Nominal Cooling Capacity Heat Type Nominal Heating Capacity Airflow Options Voltage Factory Options Special Options Product Generation FIGURE 1: PRODUCT NOMENCLATURE NOTE: LB600 matches with both HB480 and HB600 Outdoor Condensing Units for maximum effi- ciency.
DESCRIPTION Evaporator blower units are designed with two distinct mod- ules to provide maximum application flexibility. The 25, 30 and 40 ton units are shipped as single packages with the blower module mounted on top of the coil module, The blower module can be repositioned in the field to meet almost any installation requirement.
036-21335-002-A-1102 STEAM COILS (LA300 & LB360 only): A steam coil is avail- able on the 25 & 30 Ton for installation between the blower and coil modules of both horizontal and vertical units. Since the casing matches the dimensions and the finish of the basic unit, it becomes an integral part of the unit after installation.
DETAILS FOR SECURING BOTTOM MOUNTING SUPPORTS 1-1/2 HOR IZONTAL LE U360 O R 480 UNIT S US P E NDE D F R OM A B OVE The s ame channels can be used in either position. W hen used to support at vertical unit, these channels s hould be cut to match the bottom dimension of the e vaporator coil s ection.
036-21335-002-A-1102 TABLE 3: CORNER WEIGHTS Unit Weight UNIT- MODEL Shipping LA300 1180 LB360 1180 LB480 1510 LB600 1572 TABLE 4: ACCESSORY OPERATING WEIGHT DISTRIBUTION (LBS) ACCESSORY BASE HOT WATER COIL STEAM COIL 1 ROW These weights should be added to each point load in table 3. This accessory can only be applied on units installed in the vertical position.
036-21335-002-A-1102 TABLE 8: HOT WATER COIL CAPACITIES UNIT HOT WATER MODEL COIL MODEL LA300 10,000 12,000 1HW0406 10,000 LB360 12,000 14,000 12,800 LB480 16,000 19,200 1HW0407 16,000 LB600 20,000 24,000 These capacities do not include any blower motor heat. NOTE: Temperature Water Drop (ºF) = (2 X MBH) / GPM. TABLE 9: HOT WATER COIL CAPACITY CORRECTION AND PRESSURE DROP VS GPM HOT WATER COIL MODEL 1HW0406...
TABLE 10: STEAM COIL CAPACITIES UNIT STEAM COIL MODEL MODEL LA300 1NF0454 LB360 These capacities do not include any blower motor heat. Multiply these capacities by the factors in Table 11 to correct for higher steam pressure. TABLE 11: CORRECTION FACTORS FOR HIGH STEAM STEAM PRESSURE (PSIG) CAPACITY CORRECTION FACTOR NOTE: Steam Rate = (lbs/Hr.) = 1.025 x MBH...
FIGURE 13: HOT WATER COIL DIMENSIONS TABLE 14: HOT WATER COIL DIMENSIONS COIL UNIT MODEL MODEL LA300 1HW0406 LB360 LB480 1HW0407 LB600 FIGURE 14: STEAM COIL DIMENSIONS TABLE 15: STEAM COIL DIMENSIONS COIL UNIT MODEL MODEL LA300 1NF0454 LB360 Coils are field-installed between the evaporator coil and the blower section of the unit. FIGURE 15: BASE SECTION DIMENSIONS DIMENSIONS 100-1/8...
036-21335-002-A-1102 TABLE 17: PHYSICAL DATA DESCRIPTION Rows Deep X Rows High Finned Length, Inches Face Area, Feet EVAPORATOR Tube (copper) OD, Inches COIL Fins (Aluminum) per 1 inch Piping Connections, Inches CENTRIFUGAL Diameter X Width, Inches (Forward Curved) BLOWERS (2 PER UNIT) Size and Quantity Per Model, Inches FILTERS (THROWAWAY)
TABLE 19: FAN PERFORMANCE DATA - 25 TON 8,000 0.30 0.56 0.43 0.80 0.68 1.12 1.00 1.23 1.11 1.60 1.48 1.73 1.61 1.95 1.82 Unit resistance is based on a dry evaporator coil and clean filters. Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to the blower motor and drive table and the accessory static resistance table for additional information.
TABLE 21: FAN PERFORMANCE DATA - 40 TON 12,800 0.20 0.38 0.19 0.65 0.47 0.99 0.84 1.11 0.96 1.65 1.52 1.73 1.60 Unit resistance is based on a dry evaporator coil and clean filters. Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to the blower motor and drive table and the accessory static resistance table for additional information.
036-21335-002-A-1102 600 RPM Available external static pres- sure for unit accessories and the duct system. FIGURE 17: BLOWER CURVE LB480 Unitary Products Group LB480 CFM (X 100) Internal unit resistance based on a dry coil plus 2" throwaway filters. 190 200...
600 RPM AvaIlable external static pres- sure for unit accessories and the duct system. FIGURE 18: BLOWER CURVE LB600 LB600 CFM (X 100) Internal unit resistance based on a dry coil plus 1" throwaway filters. 036-21335-002-A-1102 Unitary Products Group...
036-21335-002-A-1102 EACH UNIT SHALL BE: • Covered by a 1-year limited parts warranty on the com- plete unit. • In current production with published literature available to check performance, limitations, specifications, power requirements, dimensions, operation and appearance; also equipped with a V-belt drive option that: Will permit the blower RPM to be adjusted to meet the exact CFM requirement of the system.