York EVAPORATOR BLOWERS K2EU060 Technical Manual

York EVAPORATOR BLOWERS K2EU060 Technical Manual

Split-system evaporator blowers 5 thru 15 nominal tons

Advertisement

Technical Guide
SPLIT-SYSTEM
EVAPORATOR BLOWERS
K2EU060, K4EU090, K3EU120 &
K3EU180
5 THRU 15 NOMINAL TONS
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
DESCRIPTION
These completely assembled units include a well-insulated cabinet, a
DX cooling coil with copper tubes and aluminum fins,
valve(s), distributor(s), throwaway filters, a centrifugal blower, a blower
motor, an adjustable belt drive, a blower motor contactor and a small
holding charge of refrigerant-22.
The units are shipped in the vertical position ready for field installation.
They can be installed for horizontal operation by reversing the position
of the solid bottom panel with the return air duct flange on the front of
the unit.
ACCESSORIES—FIELD INSTALLED
SUPPLY AIR PLENUMS
These fully insulated plenums are available for free standing units
located within the conditioned space, are shipped knocked-down for
easy field assembly, are finished to match the exterior of the basic
unit, and have double deflection grills that can be adjusted to vary the
throw, spread and drop of the supply air.
RETURN AIR GRILLS
These expanded metal grills are available for free standing units
located within the conditioned space, are finished to match the exterior
of the basic unit and are shipped in one piece for easy installation.
BASES
Bases are available to raise vertical units above the floor. Outdoor air
may be introduced through these bases by cutting an access opening
to accommodate the outdoor air duct connection. These bases are fin-
ished to match the exterior of the basic unit. They may have to be insu-
lated in the field for certain applications.
THREE-PHASE ELECTRIC HEATERS
Electric heaters are available in several capacities to provide maxi-
mum flexibility. Both the air conditioning unit and the heater can be
selected to precisely match the cooling and heating requirements of
the conditioned space. These heaters are designed for easy field
installation over the supply air opening of the unit. They have been
tested by and will be shipped with a CSA label. Every heater will be
fully protected against excessive current and temperature by fuses
and two high limit thermostats.
Units with electric heat will require only one power supply for both the
heating elements and the supply air blower motor, and the power wir-
ing can be protected by either dual element/time delay fuses or an
inverse time circuit breaker.
036-21300-002-A-0905
expansion

Advertisement

Table of Contents
loading

Summary of Contents for York EVAPORATOR BLOWERS K2EU060

  • Page 1 Technical Guide SPLIT-SYSTEM EVAPORATOR BLOWERS K2EU060, K4EU090, K3EU120 & K3EU180 5 THRU 15 NOMINAL TONS FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE DESCRIPTION These completely assembled units include a well-insulated cabinet, a DX cooling coil with copper tubes and aluminum fins, valve(s), distributor(s), throwaway filters, a centrifugal blower, a blower motor, an adjustable belt drive, a blower motor contactor and a small holding charge of refrigerant-22.
  • Page 2: Table Of Contents

    DESCRIPTION ........1 ACCESSORIES—FIELD INSTALLED ....1 NOMENCLATURE .
  • Page 3: Accessories-Field Installed

    036-21300-002-A-0905 NOMENCLATURE ACCESSORIES-FIELD INSTALLED (CONT.) HOT WATER COILS These drainable coils have 2 rows of 1/2" copper tubes, 12 aluminum fins per inch, a casing that is finished to match the exterior of the basic unit, but no water control valve. The coils slide out of their casings for easy field installation.
  • Page 4: Vertical And Horizontal Application Keu060, 090 & 120

    FIGURE 1 - VERTICAL AND HORIZONTAL APPLICATION KEU060, 090 & 120 FIGURE 2 - VERTICAL AND HORIZONTAL APPLICATION KEU180 036-21300-002-A-0905 MODEL 15 TON These units have two distinct modules . . . a blower module and a coil module. Although the unit is always shipped in the vertical position with a vertical air discharge as shown in illus- tration (a), the blower module can be repositioned in the field as shown in illustrations (b) and (c) for maximum flexibility.
  • Page 5: Keu180

    036-21300-002-A-0905 FIGURE 3 - SUSPENSION MOUNTING (HORIZONTAL) - KEU060, 090 AND 120 TABLE 1: UNIT SUSPENSION MOUNTING (HORIZONTAL APPLICATION) WEIGHTS Shipping Unit Model Weight (lb) K*EU060 K*EU090 K*EU120 K*EU180 TABLE 2: KEU OPERATING WEIGHTS (LBS.) MODEL BASIC UNIT ACCESSORIES Electric Heater Unitary Products Group Operating CG (in)
  • Page 6: Suspension Accessory (Horizontal)

    FIGURE 4 - SUSPENSION ACCESSORY (HORIZONTAL) - KEU180 TABLE 3: SOUND POWER RATINGS BLOWER UNIT MODEL 2,000 0.50 0.70 3,000 0.60 1.05 4,000 0.70 1.75 6,000 0.75 2.75 1. At a distance of 10 feet from the blower. NOTE: These values have been accessed using a model of sound propagation from a point source into the hemispheric free field. The dBA values provided are for reference only.
  • Page 7: Heating Capacity - Electric Heat

    036-21300-002-A-0905 TABLE 4: HEATING CAPACITY - ELECTRIC HEAT ACCESSORY UNIT MODEL HEATER MODEL 2HT045010 2HT045016 2HT045026 2HS045010 2HS045016 090, 120 2HS045026 2HS045036 2HS045010 2HS045016 2HS045026 2HS045036 2HS045072 1. Capacity Ratings do not include the heat generated by the air blower motor. 2.
  • Page 8: Pressure Drop Vs. Gpm

    TABLE 5: STEAM COIL CAPACITY STEAM COIL UNIT MODEL MODEL 1NF0450 1NF0451 1NF0452 1. These capacities do not include any blower motor heat. 2. Multiply these capacities by the following factors to correct for higher steam pressures. Steam Pressure, psig Capacity correction factor NOTE: Steam rate (lb./hr.) = 1.025 x MBH CAUTION: Do NOT operate a motor above its nominal HP rating when a unit is equipped with a steam coil acces-...
  • Page 9: Supply Air Blower Performance - Keu060 (5 Ton)

    036-21300-002-A-0905 TABLE 9: SUPPLY AIR BLOWER PERFORMANCE - KEU060 (5 TON) 1400 0.08 1600 0.24 1800 0.39 2000 0.54 2200 0.70 2400 0.88 2600 1.07 2800 1024 1187 1.27 3000 1076 1395 1.50 3200 1129 1622 1.74 1400 0.47 1600 1044 0.63 1800...
  • Page 10: Supply Air Blower Performance - Keu090 (7.5 Ton)

    TABLE 10: SUPPLY AIR BLOWER PERFORMANCE - KEU090 (7.5 TON) 2200 0.30 2400 0.44 2600 0.58 2800 0.71 3000 0.84 3200 0.97 3400 1013 1.09 3600 1120 1.20 3800 1223 1.31 4000 1322 1.42 4200 1418 1.52 4400 1510 1.62 4600 1599 1.72...
  • Page 11: Supply Air Blower Performance - Keu120 (10 Ton)

    036-21300-002-A-0905 TABLE 11: SUPPLY AIR BLOWER PERFORMANCE - KEU120 (10 TON) 2800 0.13 3000 0.37 3200 0.60 3400 0.81 3600 1.01 3800 1119 1.20 4000 1294 1.39 4200 1468 1.57 4400 1641 1.76 4600 1815 1.95 4800 1991 2.14 5000 2169 2.33 5200...
  • Page 12: Supply Air Blower Performance - Keu180 (15 Ton)

    TABLE 12: SUPPLY AIR BLOWER PERFORMANCE - KEU180 (15 TON) 4000 0.41 4200 0.66 4400 0.89 4600 1022 1.10 4800 1202 1.29 5000 1372 1.47 5200 1533 1.64 5400 1689 1.81 5600 1841 1.97 5800 1991 2.14 6000 2140 2.30 6200 2290 2.46...
  • Page 13: Static Resistance For Unit Accessories

    036-21300-002-A-0905 TABLE 13: STATIC RESISTANCE FOR UNIT ACCESSORIES (IWG) - KEU060-120 Electric Heat KW 2200 0.01 0.01 2400 0.01 0.02 2600 0.01 0.02 2800 0.01 0.03 3000 0.01 0.03 3200 0.02 0.04 3400 0.02 0.04 3600 0.02 0.05 3800 0.02 0.06 4000 0.03...
  • Page 14: Supply Air Plenum Performance Data

    TABLE 15: SUPPLY AIR PLENUM PERFORMANCE DATA Vertical Louvers (Plan Face View) Model Velocity (FPM) Spread Throw (Feet) (Feet) Min. Max. Min. Max 1600 1800 2000 2200 2400 2400 2700 3000 3300 3600 3200 3600 4000 1025 4400 1130 4800 1230 4800 5400...
  • Page 15: Description

    036-21300-002-A-0905 TABLE 17: KEU PHYSICAL DATA Component Centrifugal Blower (Dia. X Wd. in.) EVAPORATOR BLOWER Fan Motor HP (Belt Drive) EVAPORATOR COIL HOT WATER COIL STEAM COIL Quantity Per Unit (16” X 25” X 1”) AIR FILTERS Quantity Per Unit (20” X 20” X 1”) HOLDING CHARGE 1.
  • Page 16: Unit Dimensions Keu060

    FIGURE 1 - UNIT DIMENSIONS KEU060 ACCESSORIES • ELECTRIC HEATER - Add 13” to unit height when used. • SUPPLY AIR PLENUM - Add 24-1/4” to unit height when used. • BASE - Add 20” to unit height when used. TABLE 18: UNIT CLEARANCES KEU060 MINIMUM CLEARANCES Side with RETURN AIR opening...
  • Page 17: Unit Dimensions Keu090 & 120

    036-21300-002-A-0905 FIGURE 2 - UNIT DIMENSIONS KEU090 & 120 ACCESSORIES • ELECTRIC HEATER - Add 14-1/4” to unit height when used. • SUPPLY AIR PLENUM - Add 27-1/2” to unit height when used. • BASE - Add 20” to unit height when used. TABLE 19: UNIT CLEARANCES KEU090 &...
  • Page 18: Unit Dimensions Keu180

    FIGURE 3 - UNIT DIMENSIONS KEU180 ACCESSORIES • ELECTRIC HEATER - Add 14-1/4” to unit height when using 10, 16, 26, or 36 KW heater • SUPPLY AIR PLENUM - Add 27” to unit height when used. • BASE - Add 24” to unit height when used. •...
  • Page 19: Accessory Dimensions

    036-21300-002-A-0905 WITH ELECTRIC HEAT - Remove this 2-1/2” knockout from the rear panel of the plenum. Route the power wiring conduit through this opening and connect it to the field-supplied fitting on the elec- tric heat accessory. Connect the power wiring to the fuse block in the heater control box.
  • Page 20: Return Air Grill

    TABLE 21: ELECTRIC HEATER DIMENSIONS KEU060, 090, 120 & 180 Heater Nom. Unit Model Model 2HT04501025 2HT04501625 2HT04502625 2HS04501025, 46, 58 2HS04501625, 46, 58 2HS04502625, 46, 58 2HS04503625, 46, 58 2HS04507225, 46, 58 1. The 2HT heaters are not CSA approved for 060 units mounted horizontally. FIGURE 6 - RETURN AIR GRILL Grill Dimensions (Inches) Grill Model...
  • Page 21 036-21300-002-A-0905 FIGURE 8 - STEAM COIL FIGURE 9 - HOT WATER COIL Unitary Products Group Steam Coil Dimensions (inches) Coil Unit Model Model 21-7/8 1NF0450 1NF0451 1NF0451 60-3/4 32-1/4 1NF0452 1. Installs over the return air opening of the unit-before the filters. 2.
  • Page 22: Keu Electrical Data

    TABLE 22: KEU ELECTRICAL DATA Power Indoor Model Supply Motor (TONS) Voltage 2HT04501025 2HT04501625 2HT04502625 2HT04501025 2HT04501625 2HT04502625 2HS04501025 2HS04501625 2HS04502625 2HS04503625 2HS04501025 2HS04501625 2HS04502625 2HS04503625 (7.5) 2HS04501046 2HS04501646 2HS04502646 2HS04503646 2HS04501058 2HS04501658 2HS04502658 2HS04503658 2HS04501025 2HS04501625 2HS04502625 2HS04503625 2HS04501025 2HS04501625 2HS04502625 2HS04503625...
  • Page 23 036-21300-002-A-0905 TABLE 22: KEU ELECTRICAL DATA (CONTINUED) Power Indoor Model Supply Motor (TONS) Voltage 2HS04501025 2HS04501625 10.6 2HS04502625 2HS04503625 2HS04507225 2HS04501025 2HS04501625 2HS04502625 2HS04503625 2HS04507225 (15) 2HS04501046 2HS04501646 2HS04502646 2HS04503646 2HS04507246 2HS04501058 2HS04501658 2HS04502658 2HS04503658 2HS04507258 1. Dual element time delay. 2.
  • Page 24: Field Wiring For Power Supply

    FIGURE 10 - FIELD WIRING FOR POWER SUPPLY FIGURE 11 - COOLING ONLY UNIT FIGURE 12 - UNIT WITH STEAM OR HOT WATER COIL ACCESSORY 036-21300-002-A-0905 Unitary Products Group...
  • Page 25: Field Wiring For Units With Electric

    036-21300-002-A-0905 FIGURE 13 - FIELD WIRING FOR UNITS WITH ELECTRIC HEAT Unitary Products Group...
  • Page 26 036-21300-002-A-0905 Unitary Products Group...
  • Page 27 036-21300-002-A-0905 Unitary Products Group...
  • Page 28 Subject to change without notice. Printed in U.S.A. Copyright © by Unitary Products Group 2005. All rights reserved. Unitary Products Group Supersedes: 036-21300-001-A-0901 5005 York Drive 036-21300-002-A-0905 Norman 73069...