York LEU360 Technical Manual page 14

Split-system air-cooled evaporator blower 30, 40 & 50 ton
Table of Contents

Advertisement

550.13-TG2Y (799)
TABLE 16: L*EU360 SUPPLY AIR BLOWER PERFORMANCE
2
3
RPM
SP
BHP
K
10,000
600
0.48
2.8
2.4
4
0.62
3.1
2.7
635
5
0.87
3.8
3.3
700
6
1.21
4.7
4.1
775
7
1.30
4.9
4.2
800
8
1.64
5.9
5.1
875
900
1.75
6.2
5.4
9
2.10
7.2
6.2
970
1000
2.25
7.6
6.6
1.
Unit resistance is based on a wet evaporator coil and clean filters.
2.
Available static pressure in IWG to overcome the resistance of the duct system and any accessories added to the unit. Refer to
the blower motor and drive table and the accessory static resistance table for additional information.
3.
Motors can be selected to operate into the service factor because they are located in the moving air stream, upstream of any heat-
ing device. units with steam or hot water coils are the only exception. On these units, the BHP must not exceed the nominal HP
rating of the motor.
4.
Min. speed for drive accessory 1LD0415.
5.
Min. speed for drive accessory 1LD0414
6.
Min. speed for drive accessory 1LD0408
7.
Max. speed for drive accessory 1LD0415
8.
Max. speed for drive accessory 1LD0414
9.
Max. speed for drive accessory 1LD0406
14
2
3
W
W
SP
BHP
K
11,000
0.35
3.3
2.9
0.49
3.7
3.2
0.76
4.4
3.8
1.11
5.3
4.6
1.20
5.5
4.8
1.54
6.5
5.6
1.66
6.8
5.9
2.00
7.8
6.7
2.15
8.2
7.1
1
CFM
2
3
2
W
SP
BHP
SP
K
12,000
0.20
3.9
3.4
0.03
0.35
4.3
3.7
0.19
0.63
5.0
4.3
0.49
0.99
5.9
5.1
0.86
1.08
6.2
5.4
0.95
1.43
7.1
6.1
1.32
1.55
7.4
6.4
1.44
1.90
8.5
7.3
1.81
2.06
8.8
7.6
1.97
3
2
W
BHP
SP
BHP
K
13,000
14,000
4.5
3.9
4.9
4.2
0.03
5.5
5.6
4.8
0.34
6.3
6.5
5.6
0.72
7.2
6.9
6.0
0.81
7.6
7.8
6.7
1.20
8.6
8.1
7.0
1.33
8.9
9.2
7.9
1.71
10.0
9.5
8.2
1.88
10.4
Unitary Products Group