CHIMNEY CONNECTOR

Your chimney connector (commonly called stove pipe) and chimney must have the same
diameter as the stove's exhaust outlet. The stove pipe must be made of aluminized or cold roll
steel with a minimum 24-gauge thickness (0.021" or 0.53 mm). It is strictly forbidden to use
galvanized steel.
The following recommendations may be useful for the installation of your chimney connector: 
 
Your chimney connector should be assembled in such a way that the male end (crimped) faces down to 
prevent  creosote  dripping  outside  the  joints.  Attach  each  of  the  sections  to  one  another  with  three 
equidistant metal screws.  Also use three equidistant metal screws to attach the connector to the stove's 
exhaust collar.  See Figure 2.3 (A) and Figure 2.3 (B). 
The pipe must be short and straight.  All sections installed horizontally must slope at least ¼ inch per foot, 
with the upper end of the section toward the chimney. See Figure 2.3 Detail B. 
To insure a good draft, the total horizontal length of the connector should never exceed 8' to 10' (2.4 to 
3.04  m).    In  the  case  of  vertical  installation,  the  total  length  of  the  connector  can  be  much  longer  and 
connected without problem to the chimney at the ceiling level. 
There  should  never  be  more  than  two  90  degrees  elbows  in  the  whole  connector  and  chimney  system. 
Never start with a 90
o
90
 elbow. 
The  connector  must  not  pass  through  any  combustible  material,  nor  may  it  pass  through  a  concealed 
space (such as an attic, roof space, or closet). If passing through a wall, ceiling, or into a masonry chimney, 
use either chimney components listed for that specific use, or means acceptable to local authorities having 
jurisdiction over the installation. 
Installation of a "barometric draft stabiliser" (fireplace register) on a connector is not recommended. 
o
 elbow.  Always go up vertically for at least 2 feet from the flue spigot before using a 
FIGURE 2.3 (A) Connecting Sections
 
19