Optional Parts; General; Type Of Copper Pipe And Insulation Material; Additional Materials Required For Installation - Fujitsu Slim Duct Type Installation Manual

Air conditioner outdoor unit, slim duct type, r410a refrigerant
Table of Contents

Advertisement

2.5. Optional parts

Description
Model No.
Wireless Remote
UTY-LNHUM
Controller
Wired Remote
UTY-RNNUM
Controller
Simple Remote
UTY-RSNUM
Controller
IR Receiver Unit
UTY-LRHUM
Remote sensor unit
UTY-XSZX
External control set
UTD-ECS5A

3. GENERAL

This INSTALLATION MANUAL briefly outlines where and how
to install the air conditioning system. Please read over the
entire set of instructions for the indoor and outdoor units and
make sure all accessory parts listed are with the system be-
fore beginning.
] 1

3.1. Type of copper pipe and insulation material

Copper tubing for connecting the outdoor unit to the indoor
unit and insulation material is available for purchase locally.
When you purchase them, please specify the following.
• Deoxidized annealed copper pipe for refrigerant piping as:
CAUTION
Refer to the Installation Manual for the outdoor unit
for description of allowable pipe length and height
difference.
MODEL
Liquid pipe
AR9/12 model
6.35 mm (1/4 in.)
AR18 model
6.35 mm (1/4 in.)
AR24 model
6.35 mm (1/4 in.)
• Use pipe with water-resistant heat insulation.
Application
For air conditioner
operation
For air conditioner
operation
For air conditioner
operation
For the wireless
remote controller
Room temperature
sensor
For control input/
output port
Diameter
Gas pipe
9.52 mm (3/8 in.)
12.70 mm (1/2 in.)
15.88 mm (5/8 in.)
CAUTION
Install heat insulation around both the gas and liquid
pipes. Failure to do so may cause water leaks.
Use heat insulation with heat resistance above
248 °F. (Reverse cycle model only)
In addition, if the humidity level at the installation
location of the refrigerant piping is expected to
exceed 70%, install heat insulation around the
refrigerant piping. If the expected humidity level is
70-80%, use heat insulation that is 15 mm (19/32 in.)
or thicker and if the expected humidity exceeds 80%,
use heat insulation that is 20 mm (25/32 in.) or thicker.
If heat insulation is used that is not as thick as
specified, condensation may form on the surface of
the insulation. In addition, use heat insulation with
heat conductivity of 0.045 W/(m•K) or less (at 68 °F).
] 1

3.2. Additional materials required for installation

A. Refrigeration (armored) tape
B. I n s u l a t e d s t a p l e s o r c l a m p s f o r c o n n e c t i n g w i r e
(See your local electrical codes.)
C. Putty
D. Refrigeration lubricant
E. Clamps or saddles to secure refrigerant piping
] 1

3.3. Operating range

Cooling/Dry Mode
Temperature
About 64 to 90 °F
Humidity
About 80% or less
Heating Mode
About 60 to 88 °F
En-5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ar9Ar12Ar18Ar24

Table of Contents