10. REMOTE CONTROLLER SETTING

.
When detecting the room temperature
using the remote controller, please
set up the remote controller accord-
ing to the following conditions. If the
remote controller is not located prop-
erly, the correct room temperature
will not be detected, and thus abnor-
mal conditions like "not cooled" or
"not heated" will occur even if the air-
conditioner is running normally.
• Locate where an average temperature for the room
being air conditioned will be sensed.
• Do not locate directly exposed to the outlet air from
the air-conditioner.
• Locate out of direct sunlight.
• Locate away from the influence of other heat sources.
Do not touch the remote controller PC board and PC
board parts directly with your hands.
Do not wire the remote controller cable together with or
parallel to the connection cables, and power supply ca-
ble of the INDOOR UNIT and OUTDOOR UNIT, BRANCH
BOX. It may cause erroneous operation.
When installing the bus wire near a source of electro-
magnetic waves, use shielded wire.
Do not set the DIP switches, either on the air condi-
tioner or the remote controller, in any way other than
indicated in this manual that is supplied with the air
conditioner. Doing so may result in improper operation.

10.1. Installing the remote controller

Open the operation panel on the front of the remote control-
ler, remove the 2 screws indicated in the following figure, and
then remove the front case of the remote controller.
When installing the remote controller, remove the connector
from the front case. The wires may break if the connector is
not removed and the front case hangs down.
When installing the front case, connect the connector to the
front case.
SET BACK
Screws
When remote controller cable is concealed
(1) Conceal the remote controller cable.
(2) Pass the remote controller cable through the hole in the
rear case and connect the remote controller cable to the
remote controller terminal board specified in figure.
(3) Clamp the remote controller cable sheath with the binder
as shown in figure.
(4) Cut off the excess binder.
(5) Install the rear case to the wall, box, etc., with 2 screws
figure.
En-18
CAUTION
Temperature
sensor
Front case
(back side)
Rear case
Connector
1. Red
2. White
Hole
Binder
(Small)
[Example]
Box
Rear case
120 (4-23/32)
30
(1-3/16)
Hole
CAUTION
Install the remote controller wires so as not to be
direct touched with your hand.
Do not touch the remote controller PC board and PC
board parts directly with your hands.
3. Black
CAUTION
When connecting the
remote controller wires, do
not overtighten the screws.
Remote
controller cable
Connector
Screws
17
(21/32)
33.5
(1-5/16)
23
(29/32)
8
(11/32)
4.5 (3/16)
6
(1/4)
Hole × 2
Hole × 3
Unit: mm (in.)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ar9Ar12Ar18Ar24

Table of Contents