GE LP 33U Series Operating Manual page 42

50 & 60 kva
Table of Contents

Advertisement

1. Switch-ON the utility voltage from the input distribution panel.
The UPS performs a SELFTEST.
A successful termination of the tests will be indicated with Overall
test results "OK".
Commissioning cannot be continued should one or more tests result
to be negative.
Please contact in this case your Service Center.
At this stage the electronic power supply is switched ON and the
buzzer sounds.
LED 1 (utility rectifier OK) and LED 2 (utility bypass OK) must be lit.
Press "MUTE" key to reset acoustical alarm. LED Alarm remains lit.
During the first commissioning LP 33U Series requests a set up of the UPS configuration parameters
presented in the following screens.
Without such configuration it is not possible to continue with the commissioning procedure.
WARNING !
The setup of the UPS configuration parameters must be done only by QUALIFIED
AND TRAINED PERSONNEL.
The setup of mistaken values could compromise the integrity and reliability of the
UPS.
In this mode the keys perform the following functions:
Confirm the selection made and select the next parameter.
ESC
Re-establish default value.
Modify or insert the selected value.
Save the configuration of set parameters.
Configuration
DISPLAY CONFIGURATION
Select language
ESC
Configuration
UPS CONFIGURATION
Input frequency
Output frequency
Inverter voltage
ESC
Modifications reserved
OPM_LPS_3UO_50K_60K_1US_V010.doc
DISPLAY CONFIGURATION screen
Select language
:
ENGLISH
This parameter allows the choice of language used to display
the information.
UPS CONFIGURATION screen
Input frequency
:
60
Hz
Input frequency value (*60Hz).
:
60 Hz
Output frequency
:
120
V
Inverter output frequency value (*60Hz).
Inverter voltage
Output voltage PHASE/NEUTRAL of the inverter (120 V).
* Configuration of the frequency to 50Hz requires the intervention of a Service Center.
Overall test results
Test1 OK
Test7 OK
Test2 OK
Test8 OK
Test3 OK
Test9 OK
Test4 OK
Test10 OK
Test5 OK
Test11 OK
Test6 OK
Continue ►
Operating Manual LP 33U Series 30 & 40 kVA
Page 42/65