Carrier 50HX Installation, Start-Up, And Operating Instructions Manual page 24

Single packaged heat pump units sizes 024-060
Hide thumbs Also See for 50HX:
Table of Contents

Advertisement

TERMINAL
Available
Airflow (CFM)
Fig. 29—Easy Select Interface Board for Units 048-060 with ECM Blower Motor
MODE
LO-Adjust
HI-Adjust
OPTION
30-Sec On/60-Sec Off Delay
Profile (Terminal 1)
No Delay Option
(Terminal 2)
30-Sec Off Delay
(Terminal 3)
45-Sec Off Delay
(Terminal 4)
compressor starts. Energizing the contactor closes the normally-
open set of contacts supplying power to both the compressor and
outdoor (condenser) fan motor (OFM). Energizing the IFR closes
the normally-open set of contacts providing power to the IFM. On
the loss of the call for cooling, 24 v is removed from both the Y
and G terminals of the thermostat (providing the FAN switch is in
the AUTO. position), deenergizing both the contactor and IFR and
opening both the contacts supplying power to compressor/OFM
and IFM.
ECM Blower Motor Units (048–060)
Indoor Fan - With the fan switch in the ON position, 24-v is
supplied to the ECM motor through the ''G'' terminal on the
Table 5—Terminal Configuration
1
1365
AUX HEAT
RANGE
VIO
1
2
3
AC/HP SIZE
BLU
1
2
3
TYPE
BRN
AC
HPC
H P
AC/HP CFM ADJUST
BLK
LO
MED
H I
AC/HP TIME DELAY
GR Y
1
2
3
RED
JW 1
D4
D5
Table 6—CFM Adjust (Percent of CFM)
FAN ONLY
–15
15
Table 7—ECM Board Pin Selection
2
1470
Y1
1
G
P2
IFO
JW 3
W2
4
O
Y/Y2
SEC-1
4
JW 4
JW 5
SEC-2
R1
L
R2
R3
4
D3
D1
F1
D2
JW2
P1
1
COOLING
–10
10
DESCRIPTION
Used when it is desirable to allow system coils time to heat
up or cool down prior to airflow
Used for servicing or when other components are used to
perform the delay function
Preset factory setting for 50HX units
Enhances system efficiency
thermostat. This voltage provides continuous power to the indoor
(evaporator) fan motor (IFM). If the fan switch is moved back to
the AUTO position and there is not a call for heating or cooling,
24-v is removed from the ''G'' terminal and the indoor fan
remains energized for the delay timing. When the fan switch is in
AUTO, the fan cycles with either the call for heating or cooling.
Cooling- On a call for cooling, 24 v is supplied to the compressor
contactor (C) and IFM simultaneously through the ''Y'' and ''G''
terminals of the thermostat. Energizing the contactor closes the
normally open set of contacts supplying power to both the
compressor and outdoor (condenser) fan motor (OFM). On the loss
of the call for cooling, 24 v is removed from the ''Y'' and ''G''
24
3
4
1680
1840
HEATING
–10
10
C95024