Carrier 50HX Installation, Start-Up, And Operating Instructions Manual page 17

Single packaged heat pump units sizes 024-060
Hide thumbs Also See for 50HX:
Table of Contents

Advertisement

VOLTAGE
RANGE
UNIT
50HX
SIZE
V-PH
(–SERIES,
(60 HZ)
IF
Min Max
USED)
024–311
208/230-1 187
024–321
208/230-1 187
030
208/230-1 187
036
208/230-1 187
042
208/230-1 187
048–301
208/230-1 187
048–311
208/230-1 187
060
208/230-1 187
(See legend following Electrical Data chart)
Table 3—Electrical Data—50HX
COMPRESSOR OFM IFM
RLA
LRA
FLA FLA
253
11.2
56.0
1.4
2.0
253
12.1
54.0
1.4
2.0
253
15.0
73.0
1.4
2.6
253
16.0
88.0
1.2
2.6
253
20.0
104.0
1.4
3.1
253
26.4
129.0
2.1
7.2
253
20.8
109.0
2.1
7.2
253
32.1
169.0
2.1
7.2
ELECTRIC
SINGLE-POINT
HEAT
POWER SUPPLY
Single-
Point
kW
FLA
Wiring
MCA
3.75/5.00
18.1/20.8
40.3/43.4
5.60/7.50
27.1/31.3
51.0/56.5
7.50/10.0
36.1/41.7
62.5/69.5
3.75/5.00
18.1/20.8
41.4/44.5
5.60/7.50
27.1/31.3
52.2/57.7
7.50/10.0
36.1/41.7
63.7/70.7
3.75/5.00
18.1/20.8
45.3/48.8
5.60/7.50
27.1/31.3
56.6/61.8
7.50/10.0
36.1/41.7
67.9/74.8
11.30/15.0
54.1/62.0
90.4/100.3
3.75/5.00
18.1/20.8
48.3/51.7
5.60/7.50
27.1/31.3
56.6/61.8
7.50/10.0
36.1/41.7
67.9/74.8
11.30/15.0
54.1/62.0
90.4/100.3
3.75/5.00
18.1/20.8
52.1/55.5
5.60/7.50
27.1/31.3
63.3/68.6
7.50/10.0
36.1/41.7
74.6/81.6
11.30/15.0
54.1/62.0
97.1/107.0
15.0/20.0
72.2/83.3
119.8/133.7
3.75/5.00
18.1/20.8
65.2/68.3
5.60/7.50
27.1/31.3
75.9/81.4
7.50/10.0
36.1/41.7
87.4/94.4
11.30/15.0
54.1/62.0
110.2/120.4
15.0/20.0
72.2/83.3
131.8/145.9
3.75/5.00
18.1/20.8
58.2/61.3
5.60/7.50
27.1/31.3
68.9/74.4
7.50/10.0
36.1/41.7
80.4/87.4
11.30/15.0
54.1/62.0
103.2/113.4
15.0/20.0
72.2/83.3
124.8/138.9
3.75/5.00
18.1/20.8
72.0/75.5
5.60/7.50
27.1/31.3
83.3/88.5
7.50/10.0
36.1/41.7
94.6/101.5
11.30/15.0
54.1/62.0
117.1/126.9
15.0/20.0
72.2/83.3
139.6/153.5
17
(INCLUDING UNIT ONLY)
Heater
Single-
Only
Heater
Point
Dual-
Only
Max
Single-
Point
Dual-
Fuse
Point
Max
Point
or
MOCP
Fuse
Wiring
Ckt
or
MCA
Bkr
Ckt
Bkr
45/45
22.5/26.0
25/30
60/60
33.7/39.1
35/40
70/80
45.1/50.8
50/60
45/45
22.5/26.0
25/30
60/60
33.7/39.1
35/40
70/80
45.1/50.8
50/60
50/50
22.5/26.0
25/30
60/–
–/70
33.7/39.1
35/40
70/80
45.1/50.1
50/60
100/100
67.9/78.1
60/60
22.5/26.0
25/30
60/–
–/70
33.7/39.1
35/40
80/80
45.1/50.1
50/60
100/110
67.9/78.1
60/60
22.5/26.0
25/30
70/80
33.7/39.1
35/40
80/90
45.1/50.8
50/60
100/110
67.9/78.1
125/150
90.1/104.2
70/70
22.5/26.0
25/30
80/90
33.7/39.1
35/40
90/100
45.1/50.8
50/60
125/125
67.9/78.1
150/150
90.1/104.2
60/-
-/70
22.5/26.0
25/30
70/80
33.7/39.1
35/40
90/90
45.1/50.8
50/60
110/125
67.9/78.1
125/150
90.1/104.2
90/100
22.5/26.0
25/30
100/100
33.7/39.1
35/40
100/110
45.1/50.8
50/60
125/150
67.9/78.1
150/175
90.1/104.2
DUAL-POINT
POWER SUPPLY
Unit
Only
Heater
Unit
Dual-
Unit
Only
Only
Point
Only
Dual-
Dual-
Max
Dual
Point
Point
Fuse
Point
MOCP
MCA
or
MOCP
Ckt
Bkr
17.4
25/25
18.5
25/25
22.8
30/30
70/80
23.8
35/35
70/80
29.5
45/45
70/80
100/110
42.3
50/50
70/80
100/110
35.3
45/45
70/80
100/110
48.7
80/80
70/80
100/110

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

50hx02450hx03650hx04250hx04850hx060

Table of Contents