Furnace Location Relative To Cooling Equipment; Location; Hazardous Locations - Bryant 350MAV Installation, Start-Up, And Operating Instructions Manual

Series d deluxe 4-way multipoise fixed-capacity direct-vent condensing gas furnace
Table of Contents

Advertisement

FRONT
RETURN
AIR
NOTE: These furnaces are designed for a minimum continuous
return-air temperature of 60°F or intermittent operation down to 55°F
such as when used with a night setback thermostat. Return-air
temperature must not exceed a maximum of 85°F. Failure to follow
these return-air temperature limits may affect reliability of heat
exchangers, motors, and controls.
FRONT
BACK
FRONT
WARNING: Do not install furnace on its back. Safety
control operation will be adversely affected. Never con-
nect return-air ducts to back of furnace. Failure to follow
this warning could result in fire, personal injury, or death.
CAUTION: If these furnaces are used during construc-
tion when adhesives, sealers, and/or new carpets are
being installed, make sure all combustion and circulating
air requirements are followed. If operation of furnace is
required during construction, use clean outside air for
combustion and ventilation. Compounds of chlorine and
fluorine, when burned with combustion air, form acids
which will cause corrosion of heat exchangers. Some of
these compounds are found in paneling, dry wall adhe-
sives, paints, thinners, masonry cleaning materials, and
many other solvents commonly used in construction
process.
Excessive exposure to contaminated combustion air will
result in safety and performance related problems.
°F
°F
MAX 85°F
MIN 55°F
A93042
B
A
C
K
A93043
—12—
32°F MINIMUM INSTALLED
AMBIENT OR FREEZE
PROTECTION REQUIRED
CAUTION: If these furnaces are installed in an uncon-
ditioned space where ambient temperatures may be 32°F
or lower, freeze protection measures must be taken.
Provide ample space for servicing and cleaning. Always comply
with minimum fire protection clearances shown on unit's clear-
ance to combustibles label. (See Fig. 3.) Locate furnace where
available electric power and gas supplies meet specifications on
furnace rating plate.
II. FURNACE LOCATION RELATIVE TO COOLING
EQUIPMENT
The cooling coil must be installed parallel with or on downstream
side of furnace to avoid condensation in heat exchanger. When
installed parallel with a furnace, dampers or other means used to
control flow of air must prevent chilled air from entering furnace.
If dampers are manually operated, they must be equipped with a
means to prevent operation of either unit unless damper is in
full-heat or full-cool position.
III. HAZARDOUS LOCATIONS
WARNING: When furnace is installed in a residential
garage, it must be installed so that burners and ignition
sources are located a minimum of 18 in. above floor. The
furnace must be located or protected to avoid physical
damage by vehicles. When furnace is installed in a public
garage, airplane hangar, or other building having a
hazardous atmosphere, unit must be installed in accor-
dance with requirements of National Fire Protection
Association, Inc.
A93058
18-IN. MINIMUM
TO BURNERS
A93044