Sanyo SAP-K77RAX Technical & Service Manual page 33

Split system air conditioner
Table of Contents

Advertisement

7-1-2. Outdoor Unit
AVOID:
heat sources, exhaust fans, etc. (Fig. 4)
damp, humid or uneven locations.
DO:
choose a place as cool as possible.
choose a place that is well ventilated.
allow enough room around the unit for air intake/exhaust and
possible maintenance. (Fig. 5a)
provide a solid base (level concrete pad, concrete block, 10
ground level to reduce humidity and protect the unit against possible water damage and decreased service life.
(Fig. 5b)
Install cushion rubber under unit's feet to reduce vibration and noise. (Fig. 5c)
use lug bolts or equal to bolt down unit, reducing vibration and noise.
Install in a location where no antenna of a television or radio exists within 3 meters.
Air intake
Concrete
or equal
Air intake
Min. 5 cm
Min.
Air discharge
Min.
5 cm
20 cm
Fig. 5a
Anchor bolts
(4 pcs.)
Min. 10 cm
Fig. 5b
Outdoor unit
×
40 cm beams or equal), a minimum of 10 cm above
Obstacle above
Min.
Valve
2 m
side
Min.
25 cm
Ground
Min. 5 cm
Air intake
33
NO
Exhaust fan
Hot air
Fig. 4
Min.
2 m
Cushion rubber
(Locally
purchased)
Fig. 5c
Heat source