Chapter 2 Mechanical Installation

2.1.4 Installation Notes

To realize the designed performance and maximum product life, correct installation is vital. This section
should be used in conjunction with local industry standards for mechanical and electrical installations. Note
the following items:
1. The chilled water AC is designed for integrated floor installation. It should be installed on the floor of the
equipment room or computer room.
2. Before the installation, make sure that the installation environment meets the requirements (see 1.4
Environmental Requirements) and the building should be transformed to accommodate the construction work
of piping, wiring and ventilation ducts.
3. Follow the design drawings strictly when installing the equipment, and reserve the space for maintenance.
The engineering dimensions drawings provided by the manufacturer can serve as a reference.

2.2 System Installation Arrangement

2.2.1 General Arrangement

The general arrangement of the chilled water AC is shown in Figure 2-6.
Blance valve or isolation valve*
Balancing valve or isolation valve*
Chilled water inlet
Chilled water outlet
Note
1.
2.
3. *: Components are not supplied by Emerson but are recommended for proper circuit operation and maintenance.
4. After the project installation, exhaust the AC unit before filling water to ensure the efficiency of the heat exchanger.
5. In winter, the AC unit in northern area does not operate for a long term; you must empty the water in AC unit to protect the
heat exchanger from frost cracking.
Water filter
Water filler
Figure 2-6 General arrangement diagram
: Factory piping.
: Field piping (by technicians).
Liebert.PEX Chilled Water Series Air Conditioner User Manual
Isolation
Hose
Welding interface of chilled
valve
interface
water inlet and outlet
Drain valve
Exhaust valve
BPHE coil
Water flow regulating valve