Heat & Glo 6000GCF-IPILP Owner's Manual page 15

Hide thumbs Also See for 6000GCF-IPILP:
Table of Contents

Advertisement

2. Top Vent - Vertical Termination
No Elbow
Figure 5.6
Two Elbows
Figure 5.7
V
1
6 in.
Heat & Glo • 6000GCF-IPI, 6000GCF-IPILP • 2110-900 Rev. F • 6/08
V
H
Maximum
1
1
152 mm
3 ft
1 ft
305 mm
3 ft
2 ft
607 mm
6 ft
4 ft
1.2 m
12 ft
V1 + V2 + H1 = 50 ft (15.2 m) Max.
*No specifi c restrictions on this value EXCEPT
V
+ V
+ H
cannot exceed 50 ft (15.2 m)
1
2
1
V
= 6 inches (152 mm) Min.
1
V
= 50 ft. Max. (15.2 m)
1
V
= 3 ft. Min. (914mm)
1
NOTE: If installing a vertical vent/
termination off the top of the appli-
ance, the fl ue restrictor should be
used. See Section 7.D.
V
V
+ V
2
1
914 mm
*
*
914 mm
*
*
1.8 m
*
*
3.7 m
*
*
Minimum
2
*
*
*
*
15