Check Burner Refractory And Cylinder Assembly; Check And Adjust Ignition And Ionization Electrodes - Viessmann VITODENS 200-W WB2B Start-Up/Service Instructions

Wb2b series wall-mounted, natural gas-fired condensing boiler, for operation with natural gas heating input 104 to 370 mbh & 30 to 108 kw
Table of Contents

Advertisement

Steps
(continued)
S
ervice
A
Fig. 10
Checking burner gasket and cylinder assembly
S
ervice
+2
6
0
A
Fig. 11

15. Check burner refractory and cylinder assembly

Check the burner refractory ring C and cylinder burner assembly E for
damage and replace if necessary.
F
E
D4x
C

16. Check and adjust ignition and ionization electrodes

A
B3x
±
14
1
B
Initial Start-up and Service
1. Remove electrode block and
ionization electrode A.
2. Undo the three retaining clips B at
the refractory ring C and remove
refractory ring C.
3. Loosen the four Torx screws D and
remove cylinder burner assembly E
and assembly gasket F.
4. Fit and secure new cylinder burner
assembly E and new assembly
gasket F. Tighten to a torque of
3.3 lb.ft. / 4.5 Nm using a calibrated
torque wrench.
5. Reinstall refractory ring C.
6. Reinstall electrode block and
ionization electrode A. Tighten to a
torque of 3.3 lb.ft. / 4.5 Nm using a
calibrated torque wrench.
1.Check the ignition electrodes A and
ionization electrode B for wear and
contamination.
2. Clean electrodes with small brush
(not a wire brush) or emery paper.
3. Check electrode gaps. If the gaps
are not as specified, or the
electrodes are damaged, replace and
align the electrodes with new
gaskets. Tighten the electrode fixing
screws to a torque of 1.5 lb.ft. / 2
Nm using a calibrated torque
wrench.