MULTIQUIP GA6HB Operation And Parts Manual page 30

(honda gx340r2edn2/gx340r2ede2 gasoline engines)
Hide thumbs Also See for GA6HB:
Table of Contents

Advertisement

3. On the GFCI module (Figure 36), verify that the green
POWER LED is ON.
GREEN
POWER
LED
Figure 36. GFCI Module (Green LED ON)
4. Also verify that the AC voltmeter is registering a voltage
reading as indicated by Figure 41.
5. Next, press the TEsT button on the GFCI module and
verify that the green POWER LED turns OFF and the
red FAULT LED turns ON.
Figure 37. GFCI Module (Red/Fault LED ON)
6. Also verify that the main circuit breaker switch trips to
the OFF position.
Figure 38. Circuit Breaker OFF (GFCI Test)
7. Verify that the AC voltmeter (Figure 39) on the
generator reads zero volts.
pAgE 30 — ga6HB/ga6HeB 60 hz gENERATOR• OpERATiON ANd pARTs mANuAl — REv. #0 (03/13/14)
F
P
A
O
U
W
L
E
R
T
MANUAL RESET
PRESS
P
F
A
O
U
W
L
E
T
R
RED
FAULT
LED
MANUAL RESET
ON
OFF
Figure 39. AC Voltmeter (Zero Volts)
8. To restore power, press the RESET button (Figure 40)
on the GFCI module and verify that the red FAULT LED
turns OFF and the green POWER LED should turn ON
GREEN
POWER
LED
MANUAL RESET
Figure 40. GFCI Module (Green LED ON Reset)
9. Verify that the AC voltmeter is registering a voltage
reading as indicated by Figure 41.
Figure 41. AC Voltmeter (120/240V)
NOTICE
It is recommended that the GFCI unit be tested when
the generator is initially taken out of the box. Then, the
generator should be tested daily at startup.
CAuTiON
The GFCI module is designed to interrupt power when
a ground fault exists to prevent injuries and shock
hazards. dO NOT operate the generator if this test fails.
Consult a qualified electrician for repair or replacement
of the GFCI module.