Weil-McLain SlimFit Manual page 85

Commercial condensing gas-fired water boilers
Hide thumbs Also See for SlimFit:
Table of Contents

Advertisement

SlimFit
commercial condensing gas
Sola control parameter table
Figure 85
(continued) Sola CONFIGURATION VALUES — setup options — White text on black titles are configuration
groups — see Figure 62, page 61 for location of configuration group in menus
Menu/Item
Units
Lead Lag Master Configuration ADVANCED — Algorithms tab
(Use scroll arrows to toggle between Central Heat, Domestic Hot Water, Mix, Frost Protection, Outdoor reset,
Warm Weather Shutdown, Algorithms, Rate Allocation, Add Stage, Drop Stage and Modulation pages)
Lead selection
method
Lag selection
method
day hr
Lead rotation time
min
Force lead rotation
day hr
time
min
Lead Lag Master Configuration ADVANCED — Rate Allocation tab
(Use scroll arrows to toggle between Central Heat, Domestic Hot Water, Mix, Frost Protection, Outdoor reset,
Warm Weather Shutdown, Algorithms, Rate Allocation, Add Stage, Drop Stage and Modulation pages)
Base load rate
%
Lead Lag Master Configuration ADVANCED — Add Stage tab
(Use scroll arrows to toggle between Central Heat, Domestic Hot Water, Mix, Frost Protection, Outdoor reset,
Warm Weather Shutdown, Algorithms, Rate Allocation, Add Stage, Drop Stage and Modulation pages)
Method 1
Detection time 1
hr mm ss
Error threshold
°F or °C
Inter-stage delay
hr mm ss
Lead Lag Master Configuration ADVANCED — Drop Stage tab
(Use scroll arrows to toggle between Central Heat, Domestic Hot Water, Mix, Frost Protection, Outdoor reset,
Warm Weather Shutdown, Algorithms, Rate Allocation, Add Stage, Drop Stage and Modulation pages)
Method 1
Detection time 1
hr mm ss
Error threshold
°F or °C
Inter-stage delay
hr mm ss
Boiler off options
All boilers off
°F or °C
threshold
Part number 550-100-116/0713
Low
High
Default
Value
Value
Lowest
See description
measured
run time
Lowest
See description
measured
run time
45d 0h
0d 0h 0m
1d 0h 0m
0m
45d 0h
0d 0h 0m
0d 0h 0m
0m
0%
100%
40%
Use error
See description
threshold
0h 0m 0s 0h 10m 0s
0h 2m 0s
10°F
2
20
(6°C)
0h 0m 0s 18h 0m 0s
0h 2m 0s
Use error
See description
threshold
0h 0m 0s 0h 10m 0s 0h 0m 30s
10°F
2
20
(6°C)
0h 0m 0s 0h 10m 0s 0h 0m 15s
All boilers
See description
off . .
70°F
195°F
195°F
(21°C)
(91°C)
(91°C)
-
fired water boiler
(continued)
Description
• Lowest measured run time or
• Rotate in sequence order
• Lowest measured run time or
• Rotate in sequence order
Toggles lead boiler after this time has elapsed
Forces lead lag rotation
Until all boilers are firing - No boiler is requested to exceed the
common base load rate.
• Use error threshold to add stage or
• Do not add stage
Delay before adding a stage once temperature has dropped to setpoint
minus the error threshold.
Temperature drop below setpoint required before more stages are
added.
Minimum time after a stage is added before another stage can be added.
• Use error threshold to add stage or
• Do not add stage
Delay before dropping a stage once temperature has risen to setpoint
plus the error threshold.
Temperature rise above setpoint required before more stages are
dropped.
Minimum time after a stage is dropped before another stage can be
dropped.
• All boilers off at threshold (all boilers shut down at error threshold)
• Lead boiler off at threshold (only the lead boiler shuts down)
Temperature at which all boilers are turned off.
— Boiler Manual