Sola control express setup — single boiler
Zoning with zone valves —
Primary/secondary piping
[Apply for Figure 16, page 17 or Figure 17, page 18]
1. No changes are needed unless the factory default values in Fig-
ure 83 need to be adjusted.
Zoning with pumps —
Primary/secondary piping
[Apply for Figure 18, page 19]
1. Pumps
a. Connect the Boiler pump to Pump A terminals on terminal
strip D.
b. Connect the DHW pump to Pump C terminals on terminal
strip D.
c. The other pump output (Pump  B) is not used for pump
control.
Radiant heating applications
[Apply for Figure 19, page 20]
1. No changes are needed unless the factory default values in Fig-
ure 83 need to be adjusted.
See WARNING
of systems from excessive temperature. Set the Sola
temperatures appropriately for the system and provide
limit controls if necessary.
Part number 550-100-116/0713
-
fired water boiler
on page  58 regarding protection
— Boiler Manual
Analog input option — setpoint
1. Go to HOME PAGE
TRAL HEAT CONFIGURATION
a. Menu title should say Setpoint. If not, use the upper right
or left arrow to toggle to the Setpoint page.
b. Press CH Setpoint source.
c. Select S2 ( J8-6) 4–20mA.
d. Press 4mA water temperature — select water tempera-
ture at minimum signal.
e. Press 20mA water temperature — select water tempera-
ture at maximum signal.
Analog input option — modulation
1. Go to HOME PAGE
TRAL HEAT CONFIGURATION
a. Use upper right or left arrow to toggle to the Modula-
tion page.
b. Press CH modulation rate source.
c. Select S2 ( J8-6) 4–20mA and burner on/off.
2. Connect a thermostat or call for heat contact across the
T-STAT terminals on terminal strip C.
a. Modulation operates based on the 4–20mA input signal.
b. The boiler is turned on/off by the T-STAT input.

High altitude installations

For altitudes above 5,500 feet,
must be set to the proper Lightoff rate
addition, the minimum and maximum firing rates
must be set as specified for high altitude. Follow
the procedures given in "Set/verify blower speed
settings" on page 90. Failure to properly set the
firing rates could result in unreliable operation
and loss of heating.
(continued)
CONFIGURE
CH–CEN-
CONFIGURE
CH–CEN-
(above 5500 feet)
the Sola control
. In
69