12. NXL HVAC BASIC SPEED CONTROL – QUICK SETUP
This chapter provides basic setup instructions for the user of NXL HVAC inverters, when using Basic
Speed Control in HVAC applications.
What you need to know
Motor nameplate data
Nominal current
Nominal speed
Speed signal specification
Signal type (V, mA)
Range (0-10, 2-10, 0-20, 4-20)
Setup
1 Run the Start-up Wizard
Note:
Running the Start Up Wizard resets all parameters to their default values.
Hold STOP button down for 5 seconds
Select application type FAN or PUMP and confirm with ENTER
Select motor nominal speed and confirm with ENTER
Select motor nominal current and confirm with ENTER
For speed signal 0 – 10 V use AI1 (Analogue Input 1)
All settings DONE
2 Control Signal Settings for Speed Signals other than 0 – 10 V
For other selections full parameter view is needed:
P2.1.14
Parameter Conceal
For speed signal 2 – 10 V use Analogue Input 1
P2.2.6
AI1 Signal Range
For speed signal 4 – 20 mA use Analogue Input 2
P2.1.15.14
I/O Reference
For speed signal 0 – 20 mA use Analogue Input 2
P2.1.15.14
I/O Reference
P2.2.12
AI2 Signal Range
Manual Test
1 Hold LEFT down for 3-5 seconds
Control Place automatically switches to Keypad
2 Use normal keypad buttons for speed control
UP and DOWN to adjust the speed
START and STOP for control
3 Hold LEFT down for 3 seconds to return to remote control (I/O or Fieldbus)
NXL HVAC Basic speed control – Quick setup
Motor
Variable Frequency Drive
Set to 0 (not in use)
Set to 4 (2 – 10 V)
Set to 1 (AI2)
Set to 1 (AI2)
Set to 1 (0 – 20 mA)
Pump
or
Fan
Speed Signal
V signal to AI1
mA signal to AI2
Control System
95(96)
Load
Pressure
Sensor
12