Honeywell T7200D Product Data page 15

Series 2000 programmable commercial thermostats and subbases
Hide thumbs Also See for T7200D:
Table of Contents

Advertisement

T7200D,E, T7300D,E,F AND Q7300 SERIES 2000 PROGRAMMABLE COMMERCIAL THERMOSTATS AND SUBBASES
Key to Press
Heating Equipment System Test
Heat/Cool Settings
Emergency Heating Equipment System Test (T7300E,F with Q7300C,D)
Heat/Cool Settings
Cooling Equipment System Test
Heat/Cool Settings
Fan Equipment System Test
Heat/Cool Settings
Key Operation System Test
Heat/Cool Settings
Unoccupied Temp
Occupied Temp
Clear Start Time
Day
Copy
Unoccupied Start TIme
System (select models)
Fan (select models)
Set Current Day/Time
Run Program
Temporary Occupied
Occupied Start Time
Continuous Unoccupied 60 19
Table 9. Installer System Test Options.
Test
Number
10
Enter heating equipment system test.
11
Stage-one heat turns on. The system fan is also energized.
12
Stage-two heat turns on. Stage-one heat and system fan remain on.
13
Stage-three heat turns on. Stage-one and stage-two heat with the system fan are on.
12
Stage-three heat turns off.
11
Stage-two heat turns off.
10
Stage-one heat and system fan turn off.
20
Change from heating to emergency heating equipment system test (Em Heat on).
21
Fan turns on.
20
Fan and highest stage heat turns off.
30
Change from heating or emergency heating to cooling equipment system test.
31
Stage-one cooling and system fan turn on.
32
Stage-two cool turn on. Stage-one cool and system fan remain on.
33
Stage-three cool turns on (Q7300G,H only). Stage-one and stage-two cool with system
fan remain on.
32
Stage-three cool turns off.
31
Stage-two cool turns off.
30
Stage-one cool and system fan turn off.
40
Change from cooling to fan equipment system test.
41
Fan turns on.
42
High speed fan turns on (Q7300Ha, L only).
41
High speed fan turns off.
40
Fan turns off.
60 2
Change from fan to key operation system test.
60 0
Unoccupied Temp test number is displayed.
60 1
Occupied Temp test number is displayed.
60 3
Increase test number is displayed.
60 5
Decrease test number is displayed.
60 7
Clear Start Time test number is displayed.
60 8
Day test number is displayed.
60 9
Copy test number is displayed.
60 10
Unoccupied Start Time test number is displayed.
60 11
System test number is displayed.
60 12
Fan test number is displayed.
60 14
Set Current Day/Time test number is displayed.
60 15
Run Program test number is displayed.
60 16
Temporary Occupied test number is displayed.
60 17
Occupied Start Time test number is displayed.
Continuous Unoccupied test number is displayed.
Description
15
63-4355—4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents