T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES

General Considerations

Table 5 lists wiring types, sizes and distances for the T7300F/Q7300H and Excel 10 products. The Q73000H accepts 14
through 22 AWG (2.0 to 0.34 sq. mm wire).
Recommended
Wire
Wire Size
Function
(Minimum)
Thermostat
Inputs: 18 AWG
wire.
(1.0 sq mm) five
wire cable bundle.
Thermostat
Outputs/Power:
wire.
14 to 18 AWG
(2.0 to
1.0 sq mm).
LonWorks
22 AWG
Bus (Non-
(0.34 sq mm)
Plenum).
Power
14 AWG
Wiring.
(2.0 sq mm)
63-4365

Table 5. Field Wiring Reference Table.

Specification
Construction
or Requirement
Standard thermostat
wire.
NEC Class 2, 140°F
Level IV, 140°F
(60°C) rating.
(60°C) rating.
Twisted pair solid
Level IV, 140°F
conductor,
(60°C) rating.
nonshielded or
Echelon® approved
cable.
Any pair nonshielded
NEC Class II,
(use heavier wire for
140°F (60°C)
longer runs).
rating.
18
Vendor Wire Type
Honeywell AK3725
(US only), typical or
equivalent.
Honeywell AK3752
(US only), typical or
equivalent.
Honeywell AK3781
Refer to E-bus
(one twisted pair),
Wiring guidelines
AK3782 (two twisted
Users Guide
pair).
74-2865-1 for
maximum length.
Honeywell AK3754
Limited by line-loss
(14 AWG) twisted
effects on power
pair), AK3909
consumption.
(14 AWG) single
conductor or
equivalent.