Fig. 13. Typical Hookup Of T7300F/Q7300H In Three-Stage Heat, Two-Stage Cool Heat Pump System; Fig. 14. Typical Hookup Of T7300F/Q7300H In Three-Stage Heat, Two-Stage Cool Heat Pump System - Honeywell Q7300H System Engineering

Series 2000 commercial thermostats and communicating subbases
Hide thumbs Also See for Q7300H:
Table of Contents

Advertisement

T7300F/Q7300H SERIES 2000 COMMERCIAL THERMOSTATS AND COMMUNICATING SUBBASES
AS
AS
X
Y1
COMPRESSOR
CONTACTOR 1
DISCHARGE
AIR
SENSOR
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
2
USE A1 AND A2 WHEN CONTACTS ARE NORMALLY CLOSED IN OCCUPIED MODE.
USE A2 AND A3 WHEN CONTACTS ARE NORMALLY OPEN IN OCCUPIED MODE.
3
CONNECT GND TO EARTH GROUND.
4
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION DIRECTIONS.

Fig. 13. Typical hookup of T7300F/Q7300H in three-stage heat, two-stage cool heat pump system

Y2
AS
AS
X
Y1
COMPRESSOR
DISCHARGE
CONTACTOR 2
AIR
SENSOR
COMPRESSOR
CONTACTOR 1
1
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
USE ECONOMIZER INSTRUCTIONS FOR INSTALLATION INSTRUCTIONS.
3
USE A1 AND A2 WHEN CONTACTS ARE NORMALLY CLOSED IN OCCUPIED MODE.
4
CONNECT GND TO EARTH GROUND.
Fig. 14. Typical hookup of T7300F/Q7300H in three-stage heat, two-stage cool heat pump system (with O/B terminals).
63-4365
G
Y2
E
W3
W2
W1
R
EM. HT.
HEAT
ECONOMIZER
RELAY
RELAY 2
FAN
HEAT
RELAY
RELAY 3
COMPRESSOR
HEAT
CONTACTOR 2
RELAY 1
(without O/B terminals).
O
E
G
W1
B
AUX.
HEAT
FAN
HEAT
RELAY
CHANGEOVER
VALVE
EM. HT.
RELAY
COOL
CHANGEOVER
VALVE
SUBBASE
2
A1
A2 A3
C5
C4
C3
C2
C1
4
CA2
CA1
CA5
CA4
CA3
T7147 REMOTE COMFORT ADJUST MODULE
1
TRANSFORMER
SUBBASE
3
A1
A2
C5
C4
C3
R
CA5
CA4
CA3
T7147 REMOTE COMFORT ADJUST MODULE
ECONOMIZER
2
TRANSFORMER
16
EB EB
T
T
LonWorks ® BUS
T
T
LonWorks ® BUS
GND
3
L1
(HOT)
L2
M16057
C2
C1
T
T
EB EB
LonWorks ®
BUS
CA2
CA1
T
T
LonWorks ®
GND
BUS
4
1
L1
(HOT)
L2
M16056