UPS Multi-Module Installation
3.3.3

Power Cables

The wiring of power cables is similar to that of single module system except that the output of the
upstream UPS is fed into the bypass input of the downstream UPS, and the load is fed by the down-
stream UPS through its inverter or bypass. The bypass and the main input sources must be refer-
enced to the same neutral potential and input earth leakage monitoring devices, if installed, must be
located upstream of the common neutral sinking point. Refer to the instructions in 1.0 - Single Mod-
ule UPS Installation.
No control wires other than those specified for the single module configuration are required.

Figure 17 Hot standby configuration

UPSTREAM
Mains L1,
L2, L3, N
INPUT DISTRIBUTION
Bypass L1,
L2, L3, N
CB1
RECTIFIER
STATIC
SWITCH
INVERTER
L1, L2, L3, N
UPS1
OUTPUT
30
DOWNSTREAM
Mains L1,
L2, L3, N
CB1
L1, L2, L3, N
TO LOAD
Bypass L1,
L2, L3, N