Wiring Subbase Connections - Honeywell RM7800E Installation Instructions Manual

7800 series relay modules
Hide thumbs Also See for RM7800E:
Table of Contents

Advertisement

120V ALARM
BURNER MOTOR
(BLOWER)
BURNER
CONTROLLER/LIMITS
LOCKOUT INTERLOCKS
(INC. AIR FLOW SWITCH)
10 SEC. INTERRUPTED
PILOT/IGNITION
MAIN FUEL VALVE(S)
5 SECOND IGNITION
(EARLY SPARK
TERMINATION)
FLAME DETECTOR
3
INITIATE
(INITIAL
00
POWERUP
ONLY)
STANDBY
POWER
POWER
LED
DISPLAY
BURNER
OPERATING
CONTROLS
AND
INTERLOCK. CHECK
INTERLOCKS
PREIGNITION INTERLOCK CLOSED
1
FLAME
SAFE START CHECK
SIGNAL
FIRING
RATE
MOTOR
1
FOR THE R7800/R7840E: THE HIGH FIRE SWITCH MUST BE WIRED CORRECTLY TO PERFORM ENERGY SAVING PURGE
FUNCTIONS. THE BURNER/BLOWER MOTOR DOES NOT START UNTIL THE HIGH FIRE SWITCH MAKES.
2
RM7800L1053, RM7840L1026: TERMINAL 21 PROVIDES INTERMITTENT PILOT FUNCTION.
Fig. 2. Wiring subbase and sequence for RM7800E,L/RM7840E,L.
RM7800E,G,L,M; RM7840E,G,L,M 7800 SERIES RELAY MODULES
SERIES 90
FIRING RATE
Q7800
MOTOR
HIGH FIRE
G
12
B
COMMON
L2
13
R
LOW FIRE
14
W
3
MODULATE
4
(L1)
15
5
16
6
17
4
LOW FIRE
7
18
START SWITCH
HIGH FIRE
8
19
PURGE SWITCH
9
20
PREIGNITION
INTERLOCK
10
21
15 SEC.
INTERRUPTED
PILOT VALVE
22
F
MASTER
SWITCH
RM7800/RM7840E,L
PREPURGE
PREPURGE
HOLD
HOLD
00
00
00
DRIVE TO
TIMED
DRIVE TO
HIGH FIRE
PREPURGE
LOW FIRE
POWER
POWER
POWER
PILOT
PILOT
FLAME
FLAME
MAIN
MAIN
ALARM
ALARM
BURNER/BLOWER MOTOR
1
10
LIMITS AND BURNER CONTROLLER CLOSED
LOCKOUT INTERLOCKS CLOSED
4
TO
20
5
TO
19
HIGH FIRE SW.
SWITCHING
13
TO
12
MOTOR ACTION
7
SERIES 90
CONTROLLER
B
FOR DIRECT SPARK IGNITION (OIL
OR GAS)
R
10
W
8
9
1
120V, 50/60 Hz POWER SUPPLY. PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2
RM7800/7840E ONLY: HIGH FIRE PURGE SWITCH
2
CONNECTED TO
4
(L1), NOT
3
SEE FLAME DETECTOR INSTALLATION INSTRUCTIONS
5
FOR CORRECT WIRING.
DO NOT WIRE TO ANY UNUSED TERMINALS.
4
RM7840L1026, RM7800L1053 HAVE INTERMITTENT
5
PILOT VALVE FUNCTIONS.
L1
(HOT)
1
L2
PFEP
10 SEC.
10
20
25
00
(4 SEC. IF
JR1 CLIPPED
MFEP
RUN
POWER
POWER
POWER
PILOT
PILOT
PILOT
FLAME
FLAME
FLAME
MAIN
MAIN
MAIN
ALARM
ALARM
ALARM
5
IGN.
5 SEC.
10 SEC. IGN./PILOT 8
15 SEC. PILOT
21
2
MAIN VALVE
9
TO
L1
6
6
TO
7
LOW FIRE SW.
5
TO
18
FLAME PROVING
13
TO
15
13
14
TO
IGNITION
TRANSFORMER
L2
2ND STAGE
FUEL VALVE
(OPTIONAL)
5
.
M12261C
15
POSTPURGE
STANDBY
POWER
POWER
IC
PII
SSC
TO
13
14
M12263D
66-1085—04