Setting The Air/Gas Ratio - Worcester GREENSTAR 24i junior Instruction Manual

Wall hung rsf gas fired condensing combination boiler, for sealed central heating systems and mains fed domestic hot water
Table of Contents

Advertisement

THIS PAGE SHOWS THE SETTING PROCEDURE FOR THE DUNGS
VALVE FOR ALTERNATIVE VALVES SEE PAGE 54 FOR SIT.
A
Please note: The flue gas test point can be
accessed on the appliance flue elbow by
removing cap D
D
INSTALLATION & SERVICING INSTRUCTIONS FOR WORCESTER GREENSTAR 24 i junior/28 i junior
8 716 115 166b (03/2009)
30.1
C
Inlet Test Nipple
30.2
30.3
B
30.4
30.5
C
SETTING THE GAS / AIR RATIO
FOR DUNGS GB-ND 055 DO1 S20
THE SETTING OF THE GAS RATIO MUST BE
CARRIED OUT BY A COMPETENT PERSON.
SETTING OF THE GAS RATIO MUST NOT BE
AT T E M P T E D
U N L E S S
T H E
C A R R Y I N G O U T T H E C O N V E R S I O N I S
EQUIPPED WITH A COMBUSTION ANALYSER
C O N F O R M I N G
TO
B S
79 2 7
COMPETENT IN ITS USE.
30. Setting the CO/CO
2
Note: When running in the service mode, the
boiler will operate both the central heating &
DHW circuits. This is to allow sufficient time for
the setting procedure. It will be necessary to run
sufficient water through the DHW circuit to
ensure that the boiler will not cycle on low
heating demands.
30.1 Connect manometer to inlet pressure point
on the gas valve.
To adjust the CO/CO
it will be necessary to
2
first operate the boiler at maximum output.
Press and hold down the service button (A) for
10 seconds until illuminated. The blue power
indicator will flash.
30.2 Turn central heating control to maximum;
the boiler will then go to maximum output.
NOTE: The control will resume normal operation
after 15 minutes or if the service button is
pressed for over a second.
30.3 Using a 2mm hexagonal ball driver set the
CO/CO
via adjuster (B)
2
using table below.
CO/CO
settings for Greenstar i Junior
2
N
. CO/CO
should be measured
OTE
2
after 10 minutes
Gas type
CO
setting
2
maximum
Natural gas
9.8% ± 0.5%
LPG
11.0% ± 0.5%
CO - less than 200ppm (0.002 ratio)
Check CO is less than 200ppm.
Measure the inlet pressure; it should be no
less than 37mb for LPG.
30.4 Set the central heating control to
minimum. The boiler will go to minimum
power.
30.5 Measure the CO/CO
and check against the
2
table above. If required adjust (C) on the gas
valve, using a 2mm hexagonal ball driver,
until the correct measurement is set.
Check CO is less than 200ppm
Return to maximum and re-check the
CO/CO
. If correct press and hold down the
2
service button for 2 seconds; the button will
cease to be illuminated and the blue power
indicator will be permanently illuminated.
Remove manometer and re-seal inlet pressure
point on gas valve.
Re-assemble and refit boiler case.
REPLACEMENT OF PARTS
P E R S O N
A N D
I S
CO
setting
2
minimum
9.2% ± 0.5%
10.5% ± 0.5%
55