Electric Characteristics - Daikin J-Series Engineeiring Data

J-series cooling only/heat pump
Hide thumbs Also See for J-Series:
Table of Contents

Advertisement

EDUS041011

10. Electric Characteristics

Representative Unit Combination
Indoor Unit
Outdoor Unit
FTKS09JEVJU
RKS09JEVJU
FTKS12JEVJU
RKS12JEVJU
FTXS09JEVJU
RXS09JEVJU
FTXS12JEVJU
RXS12JEVJU
Symbols:
MCA
: MIN. CIRCUIT AMPS (A)
MOP
: MAX OVERCURRENT PROTECTION
RLA
: RATED LOAD AMPS (A)
OFM
: OUTDOOR FAN MOTOR
IFM
: INDOOR FAN MOTOR
FLA
: FULL LOAD AMPS (A)
W
: FAN MOTOR RATED OUTPUT (W)
Room Air Conditioners J-Series
Power Supply
Hz-Volts
Voltage Range
60-208
MAX. 60Hz 253V
MIN. 60Hz 187V
60-230
60-208
MAX. 60Hz 253V
MIN. 60Hz 187V
60-230
60-208
MAX. 60Hz 253V
MIN. 60Hz 187V
60-230
60-208
MAX. 60Hz 253V
MIN. 60Hz 187V
60-230
COMP
MCA
MOP
RLA
3.7
4.4
15
3.4
3.7
4.4
15
3.4
3.7
4.3
15
3.3
4.4
5.2
15
4.0
Note:
1. Maximum allowable voltage variation between phases is 2%.
2. Select wire size based on the larger value of MCA.
3. Instead of fuse, use circuit breaker.
4. Be sure to install a ground leak detector. (One that can handle
higher harmonics.)
(This unit uses an inverter, which means that it must use a ground
leak detector capable handling high harmonics in order to prevent
malfunctioning of the ground leak detector itself.)
Electric Characteristics
OFM
IFM
W
FLA
W
FLA
0.19
0.20
33
40
0.17
0.18
0.19
0.20
33
40
0.17
0.18
0.19
0.20
33
40
0.17
0.18
0.19
0.20
33
40
0.17
0.18
3D066179B