Heat Controller, Inc.
WARNING!
WARNING! HAZARDOUS VOLTAGE! DISCONNECT
ALL ELECTRIC POWER INCLUDING REMOTE
DISCONNECTS BEFORE SERVICING.
Failure to disconnect power before servicing can cause
severe personal injury or death.
See " Unit
Yes
short
cycles"
Yes
See " Only
Fan Runs"
See " Only
Yes
Comp
Runs"
See " Does
No
not Operate
in Clg"
DXM2 PROCESS FLOW CHART
DXM2 Functional
Start
Troubleshooting Flow Chart
Did Unit
No
Attempt to
Start?
Yes
Did Unit
Yes
Lockout at
Start-up?
No
Unit Short
Cycles?
No
Only Fan
Runs?
No
Only
Compressor
Runs?
No
Did unit lockout
Yes
after a period of
operation?
No
Does unit
operate in
cooling?
Yes
Unit is OK!
'See Performance
Troubleshooting' for
further help
HEV/H SERIES
Check Main
power (see power
problems)
Check fault LED code
on control board
See
See HP/
HPWS
LP/LOC
Fault
Fault
See LT2
Condensate
Fault
43
Installation, Operation & Maintenance
See LT1
Fault
See
See Over/
Under
Fault
Voltage
No fault
shown
Replace
DXM2