Heat Controller, Inc.
Starting/Commissioning Conditions
Table 9b: Commissioning Limits
Commissioning Limits
Air Limits
Min. ambient air, DB
Rated ambient air, DB
Max. ambient air, DB
Min. entering air, DB/WB
Rated entering air, DB/WB
Max. entering air, DB/WB
Water Limits
Min. entering water
Normal entering water
Max. entering water
Normal Water Flow
HEV/H SERIES
HE Series
Cooling
45°F [7°C]
80.6° [27°C]
110° [43°C]
50/45°F [10/7°C]
80.6/66.2°F [27/19°C]
110/83°F [43/28°C]
30°F [-1°C]
50-110°F [10-43°C]
120°F [49°C]
1.5 to 3.0 gpm/ton
[1.6 to 3.2 l/m per KWI
Heating
39°F [4°C]
68° [20°C]
85° [29°C]
40°F [4.5°C]
68°F [20°C]
80°F [27°C]
20°F [-6.7°C]
30-70°F [-1 to 21°C]
90°F [32°C]
35