Electrical - Line Voltage; Series - Heat Controller HTV Series Installation, Operation & Maintenance Manual

Htv/htd/hth series two-stage geothermal heat pumps 2 to 6 tons
Table of Contents

Advertisement

Installation, Operation & Maintenance

Electrical - Line Voltage

WARNING!
WARNING! To avoid possible injury or death due to electrical
shock, open the power supply disconnect switch and secure it
in an open position during installation.
Table 4a: HT Series Electrical Data
All TT Units with Emerson ECM Fan Motor
HT
Compressor
Model
Pump
RLA
LRA
Qty
026
11.7
58.3
1
024
036
038
15.3
83.0
1
048
049
21.2
104.0
1
060
064
27.1
152.9
1
070
072
29.7
179.2
1
Rated Voltage of 208-230/60/1
HACR circuit breaker in USA only
HTV/HTD/HTH SERIES
HT
TT Units (ECM) Standard
Ext
HWG
Fan
Total
Loop
Motor
Unit
Pump
FLA
FLA
FLA
FLA
0.5
1.7
3.9
16.1
0.5
1.7
3.9
19.7
0.5
1.7
6.9
28.6
0.5
1.7
6.9
34.5
0.5
1.7
6.9
37.1
CAUTION! Use only copper conductors for fi eld installed
electrical wiring. Unit terminals are not designed to accept other
types of conductors.
HT
TT Units (ECM) with ClimaDry
Max
Min
ClimaDry
Total
Fuse/
Circuit
Pump
HACR
Amps
FLA
(2)
19.0
30
0.8
16.9
23.5
35
0.8
20.5
33.9
50
1.1
29.7
41.2
60
1.1
35.6
44.5
70
1.1
38.2
Min/Max Voltage of 197/254
All fuses Class RK-5
19
CAUTION!
Max/
Min
Fuse
Unit
Circuit
HACR
FLA
Amps
(2)
19.8
30
24.3
35
35.0
50
42.3
60
45.6
70