HE
Volt
Rated Voltage
Model
Code
024
1
208-230/60/1
030
1
208-230/60/1
036
1
208-230/60/1
042
1
208-230/60/1
048
1
208-230/60/1
060
1
208-230/60/1
HACR circuit break in U.S. only
All fuses Class RK-5
HEV-HEH SEriES
HEV/H SERIES
Compressor
Voltage
Min/Max
RLA
LRA
Qty
197/252
11.7
58.3
1
197/252
13.1
73.0
1
197/252
15.3
83.0
1
197/252
17.9
96.0
1
197/252
21.2
104.0
1
197/252
27.1
152.9
1
Wire length based on one way measurement with 2% voltage drop
Wire sizes based on 140°F (60°C) copper conductor
30
Ext
HWG
Fan
Total
Loop
Pump
Motor
Unit
Pump
FLA
FLA
FLA
FLA
0.5
4.0
3.9
20.1
0.5
4.0
3.9
21.5
0.5
4.0
3.9
23.7
0.5
4.0
5.2
27.6
0.5
4.0
5.2
30.9
0.5
4.0
6.9
38.5
Heat Controller
Heat Controller, LLC
Min
Max
Circuit
Fuse/
Amp
HACR
23.0
30
24.7
35
27.5
40
32.0
45
36.2
50
45.2
70