ELECTRICAL - POWER & LOW VOLTAGE WIRING
Figure 17: PSC Motor Speed Selection
Connect the blue wire to:
H for High speed fan
M for Medium speed fan
L for Low speed fan
Medium is factory setting
Fan Motor

ELECTRICAL - LOW VOLTAGE WIRING

Thermostat Connections
The thermostat should be wired directly to the CXM
board.
Conectar el cable azul a:
H para velocidad de ventilador alta
M para velocidad de ventilador media
Azul
L para velocidad de ventilador baja
La configuración de fábrica es velocidad media
H M L
Figure 19: Low Voltage Field Wiring
Fan Motor
Motor del Ventilador
Low Water Temperature Cutout
The CXM control senses low water temperature
utilizing thermistor FP1. Note that the FP1 thermistor is
located on the refrigerant line between the coaxial heat
exchanger and the cap tube. Therefore, FP1 is sensing
refrigerant temperature, not water temperature, which is
a better indication of how water flow rate/temperature is
affecting the refrigeration circuit.
The factory setting for FP1 is 0°F [-1.1°C] refrigerant
temperature. HC series equipment is not rated for
extended range applications.
18
� CAUTION! �
CAUTION! - HC Series equipment may not
be used when EWT is below 60°F [15°C].