GENERATOR AC VOLTAGE CONNECTIONS
DESCRIPTION
The regulator is equipped with seven numbered tenninals (0
to 6) and their related brass jumpers. The illustrations show
connection points and jumpers for the 3 phase configuration
of the generator. The sensing leads connect between pin #1
and pin #2 on the AC tenninal block and connection #2 and
#0
on the voltage regulator board.
NOTE:
Series Delta requires the installation of a jumper on
the regulator boanl between terminal Band J O.
BLK AVR
U1
CASE GND
L1
V1
L2
L3
GRN AVR
BlK AVR
,,~
_ _ _ _ _ _ _ _
~
U1
V1
W1
CASE GND
170 - 270 V
180-160V
L1
L2
L3
GRN GND
BE THREE PHASE (SIX WIRE)
o
3 PHASE VOLTAGE REGULATOR
PARAllEL WYE (STAR)
L-N -120 VAC 10 60 Hz
L-N -110 VAC 10 60 Hz
SERIES WYE (STAR)
~
s
Ll
~
~
L3
L-L- 450 VAC 30 60 Hz
L-N - 265 VAC 10 60 Hz
N
BE THREE PHASE (TWELVE WIRE)
-.yo
WESTERBEKE
Engines & Generators
30
SERIES DELTA
L-L- 240 VAC 30 60 Hz
L2, L3-N - 120 VAC 1060 Hz
A. SERIES DELTA - Note the
repositioning 01 the ground
lead Irom neutral to gener-
ator housing.
J. Jumper using 1110 AWG
Wire.