Kidde PE9 User Manual page 3

9 volt battery-operated photoelectric smoke alarm
Hide thumbs Also See for PE9:
Table of Contents

Advertisement

Ceiling mounting is preferred in ordinary residential construction.
• For mobile home installation, select locations carefully to avoid
thermal barriers that may form at the ceiling. For more details,
see MOBILE HOME INSTALLATION below.
• When mounting an alarm on the ceiling, locate it at a minimum
of 4" (10cm) from the side wall (see figure 1).
• When mounting the alarm on the wall, use an inside wall with
the top edge of the alarm at a minimum of 4" (10cm) and a
maximum of 12" (30.5cm) below the ceiling (see figure 1).
• Put smoke alarms at both ends of a bedroom hallway or large
room if the hallway or room is more than 30 ft (9.1m) long.
• Install Smoke Alarms on sloped, peaked or cathedral ceilings at
or within 3 ft (0.9m) of the highest point (measured horizontal-
ly). NFPA 72 states: "Smoke alarms in rooms with ceiling slopes
greater than 1 ft in 8 ft (.3m in 2.4m) horizontally shall be locat-
ed on the high side of the room." NFPA 72 states: "A row of
alarms shall be spaced and located within 3 ft (0.9m) of the
peak of the ceiling measured horizontally" (see figure 3).
FIGURE 1
FIGURE 2
FIGURE 3