Daikin FXFQ09PVJU Installation Manual page 9

Vrv system inverter heat pump
Hide thumbs Also See for FXFQ09PVJU:
Table of Contents

Advertisement

Installation is possible when ceiling opening dimensions is as follows
• When installing the unit within the frame for fixing false ceiling.
33-1/16
35-7/8
(Dimension inside frame)
Fig. 6
NOTE
• Installation is possible with a ceiling dimension of 35-7/8in. (marked with *). However, to achieve a ceiling-
panel overlapping dimension of 13/16in., the spacing between the ceiling and the unit should be 1-3/8in. or
less. If the spacing between ceiling and the unit is over 1-3/8in., attach ceiling material to
recover the ceiling.
Ceiling material
(2) Make the ceiling opening needed for installation where applicable. (For existing ceilings)
• Refer to the paper pattern for installation (5) for ceiling opening dimensions.
• Create the ceiling opening required for installation. From the side of the opening to the casing outlet,
implement the refrigerant and drain piping and wiring for remote controller (unnecessary for wireless
type) and indoor-outdoor unit casing outlet. Refer to "6. REFRIGERANT PIPING WORK", "7. DRAIN
PIPING WORK" and "8. ELECTRIC WIRING WORK".
• After making an opening in the ceiling, it may be necessary to reinforce ceiling beams to keep the ceiling
level and to prevent it from vibrating. Consult the builder for details.
(3) Install the suspension bolts.
(Use either a M8~M10 size bolt or the equivalent)
Use a hole-in anchor for existing ceilings, and a
sunken insert, sunken anchor or other field sup-
plied parts for new ceilings to reinforce the ceiling
to bear the weight of the unit. Adjust clearance
(2-4in.) from the ceiling before proceeding
further.
NOTE
• All the above parts are field supplied.
8
Frame
False
ceiling
≥13/16
1-3/8
Fig. 8
33-7/8
(Opening dimension inside
the flame for ceiling)
33-7/8 – *35-7/8
(Ceiling opening dimension)
Fig. 7
(Unit: in.)
1-3/8
<installation example>
Anchor
Long nut or turn-buckle
Suspension bolt
False ceiling
Fig. 9
(Unit: in.)
≥13/16
(Ceiling-panel
overlapping dimension)
part or
(Unit: in.)
Ceiling slab
English

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents