Connecting the Assembly Cable

Indoor
N(1)
1
2
unit
1
1
2
E
N1
N(1)
N(1)
1
2
E
Outdoor
N(1)
1
2
unit
8
E-
The outdoor unit is powered from the indoor unit via the assembly cable.
If the outdoor unit is more than five metres away from the indoor unit,
the cable must first be extended to a maximum of 15 metres.
1
Extend the assembly cable if necessary.
2
Open the front grille by pulling on the tabs on the lower right and left sides of
the indoor unit.
3
Remove the screw securing the connector cover.
4
Pass the assembly cable through the rear of the indoor unit and connect the
assembly cable to terminals as shown in the figure.
Each wire is labeled with the corresponding terminal number.
5
Pass the other end of the cable through the 65 mm hole in the wall.
6
Replace the connector cover, carefully tightening the screw.
7
Close the front grille.
8
Remove the terminal board cover on the side of the outdoor unit.
9
Connect the cables to terminals as shown in the figure.
Each wire is labeled with the corresponding terminal number.
10
Connect the earth wires to the earth terminals.
11
Replace the terminal board cover, carefully tightening the screw.
12
Connect the power cable with the indoor unit.
Specially for Russian and European market, before installation,
the supply authority should be consulted to determine the
supply system impedance to ensure compliance.
Power cable specification
Power cable
3G, 1.5mm
2
,
10/16A
H05VV-F
Connect the power cable to the auxiliary circuit breaker.
An all pole disconnection from the power supply must be
incorporated in the fixed wiring ( 3mm).
Interconnection
Power plug or
circuit breaker
cable
Power plug with
4G, 1.5mm
2
H07RN-F
(More than 15A)
earth pole.