System Defaults - Heatcraft Refrigeration Products II Installation & Operating Instructions Manual

Mccu condensing units
Table of Contents

Advertisement

System Defaults

Table 5. System Defaults
Parameters
Refrigerant
Box Temperature
Superheat
Slave Evaporator
No. of Defrosts Per Day
Defrost Fail-Safe Time
Defrost End Temperature
Defrost Delay Start Time
Alarm High Temperature
Alarm Low Temperature
Alarm Time
Temperature Units
Figure 15. Control Sensor And Piping
Beacon II Controller
Code
rEF
bot
SUP
SLA
dFn
dFF
dFt
dFS
ALH
ALL
ALt
F-C
25
Air
Electric
R22
R404A
35°F
-10°F
8°F
8°F
No
No
2
4
40 min.
30 min.
45°F
60°F
0 hrs.
0 hrs.
50°F
5°F
30°F
-15°F
60 min.
60 min.
°F
°F