Heatcraft Refrigeration Products II Installation & Operating Instructions Manual page 17

Mccu condensing units
Table of Contents

Advertisement

Programming And Reviewing Settings/Changes
The Program Review button is used to program, review and change all program settings for the system.
Press "PROGRAM REVIEW" button. The Setpoint item will appear on the LED. After a few seconds delay
the Setpoint value will display. Each time the button is pressed a different setpoint item is displayed.
PROGRAM
REVIEW
Next, use the "SELECT" knob to change value of Setpoint Item.
SELECT
Next, when the desired value is selected, press the "ENTER" button to place it in program memory. If the
"ENTER" button is not pressed, the value will not be stored in the memory and thus will not be changed.
ENTER
"PROGRAM REVIEW" ITEMS
A-E
Set Defrost Type (
rEF
Set Refrigerant Type (R22, R404A or R507)
bot
Set Box Temperature (-30°F to +70°F)
SUP
Set Superheat (4°F to 20°F)
SLA
Set Board as a Slave (Yes or No)
dFn
Set Number of Defrosts Per Day (1, 2, 3, 4, 5, 6, 8, 10 or 12 per day)
dFF
Set Defrost Fail-safe Time (10 to 200 minutes)
dFt
Set Defrost End Temperature (40°F to 100°F)
dFS
Set Defrost Delay Start Time (0.5 Hours to 23.5 Hours)
ALH
Set Alarm High Temperature (-40°F to 90°F)
ALL
Set Alarm Low Temperature (-40°F to 90°F)
ALt
Set Alarm Time (2 to 120 minutes)
F-C
Set Fahrenheit/Celsius Temperature Units (°F / °C)
Beacon II Controller
Air
ELE
or
)
17