Serial Number Label Location; Clearances To Combustibles - Quadra-Fire 820-0721 Owner's Manual

Hearth and home technologies 5700 wood stove owner's manual installation and operation
Table of Contents

Advertisement

5700 ACT Wood Stove
BACkWALL / SIDEWALL
A
b
C
D
CORNER INSTALLATION
e
F
e
F
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS In Inches and (Millimeters)
NOTE: All "A", "C" and "F" Dimensions are to the inside diameter of the flue collar.
INSTALLATION: Full Vertical OR Horizontal with 2 foot minimum vertical Off Stove Top
SINGLE WALL PIPE
DOUBLE WALL PIPE
INSTALLATION: 90
DOUBLE WALL PIPE
INSTALLATION: ALCOVE
pipe with UL103 HT listed factory-built Class "A" chimney, or a masonry chimney. (Mobile Home
must be equipped with a spark arrestor). Maximum depth of Alcove shall be no more than
48"(1220mm) with a minimum height of 45.5" (1156mm) to top of unit, and the referenced
clearances.
DOUBLE WALL PIPE
*
NFPA MINIMUM CLEARANCES - NOT TESTED
**
SEE PIPE MANUFACTURERS CLEARANCES - NOT TESTED
Page 6
CLEARANCES TO COMBUSTIBLES (UL AND ULC)
90° OFF TOP
UP & OUT CEILING
CLEARANCE
STOVE TO CEILING
CLEARANCE
A
b
12.5 (318) 8 (203) 25.5 (648) 15 (381) 2 (51) 13 (432) 45.5 (1156) 18 (457)
9.5 (241) 5 (127) 25.5 (648) 15 (381) 2 (51) 13 (432) 45.5 (1156) 12 (305)
o
ELBOW OFF TOP OF STOVE THROUGH BACkWALL
9.5 (241) 5 (127) 25.5 (648) 15 (381) 2 (51) 13 (432) 45.5 (1156) 12 (305)
Six inch (6") (152mm) diameter listed Double Wall air insulated connector
10.5 (268) 6 (153) 25.5 (648) 15 (381)
SERIAL NUMBER / SAFETY LABEL LOCATION:
ON BACk OF STOVE
250-7090e
*
H
g
C
D
e
N/A
N/A
ALCOVE SIDE VIEW
g
A
B
ALCOVE TOP VIEW
C
D
F
g
H
*
45.5 (1156)
**