E. Install Outside Air Kit
Keep duct runs short and straight to minimize restriction.
A small dip is acceptable for a cold air trap.
The outside air kit must be installed using the outside
air cover (see Dimensions, Section 13.A. for location).
Locate the outside air hood in a clear area, preferably
into prevailing wind during the heating season. Refer to
Figure 5.2.
Install as shown in Figures 7.3, 7.4 and 7.5.
The air duct may be run vertically.
The outside air hood must be at least 3 ft (.91 m) below
the top of the uppermost chimney section.
CAUTION! Risk of Fire or Asphyxiation! DO NOT
draw outside combustion air from wall, fl oor or ceiling
cavity, or enclosed spaces such as an attic or garage.
• DO NOT place outside air hood close to exhaust
vents or chimneys. Fumes or odor could be drawn
into the room through the fi replace.
• Locate outside air inlet to prevent blockage from
leaves, snow/ice, or other debris. Blockages could
cause combustion air starvation.
Flexible Duct
(not supplied)
Outside Air
Hood
2 Wire Ties
Figure 7.5
Outside Air Installation
Outside Air
Plate
Assembly
Heat & Glo • HST-48D US-CAN • 4012-040 • Rev F • 11/08