Clearances - Heatilator Wood Burning Fireplace A36CH Owner's Manual

Installation and operation wood burning fireplace
Hide thumbs Also See for Wood Burning Fireplace A36CH:
Table of Contents

Advertisement

B. Clearances
WARNING! Risk of Fire! You must comply with all minimum air space clearances to combustibles as specifi ed in Fig-
ure 6.2. DO NOT pack required air spaces with insulation or other materials.
Figure 3.2
Storm Collar
Roof Flashing
(attic)
(insulation)
2 in. (51 mm) min.
Ceiling Firestop
Adapter attached here
(not shown)
48 in.
1219 mm
0 in.
to floor
Clearances to Combustible Materials
Note: Chimney air kit not shown, but required in Canada.
Heatilator • A36C & A42C • 28396 • Rev AG • 11/08
Shaded areas
represent
2 in. (51 mm) min.
air space clearance
required around pipe
Attic
Insulation
Shield
(ceiling)
Offset/Return (secured
with hanger straps)
(ceiling)
Must have 2 in. (51 mm)
minimum clearance
to header
0 in. to level
of standoffs
3/4 in. (19 mm) to back &
sides of appliance
(except at nailing flanges
where it is 1/2 in. [13 mm])
19