Jumper/Terminal Connections and Functions

The following table shows how jumpers JP1 and JP2 are set for use with the analog
input terminal connections RR and IV. Jumper numbers and settings which are shown in
this table are applicable to all printed wiring boards (see page 5-3 for terminal block
and jumper details).
Terminal/Jumper Connections for Input Reference Signals
JP1
I
V
10V
1
I
V
N/A
2
I
V
N/A
3
I
V
N/A
4
10V
N/A
5
I
V
10V
6
* 3K ohm pot divides voltage between terminal PP and CC return. Any pot value between 1K to 10K ohms
can be used but makes adjustment more sensitive.
TOSHIBA
JP2
Terminal Connections
No external connections; JP1 and
5V
JP2 should be set as shown for
keypad operation (normal factory
setting).
PP
RR
0-20mA
(4-20mA)
PP
RR
0-5Vdc
PP
RR
+
15K ohm
5V
PP
RR
+
+
* 3K ohm
5V
PP
RR
+
+
SW
5 - 4
Use when not inputting any external
reference signals into terminal RR or
IV. P.PrG parameter #2 "priority of RR
terminal input" is N/A.
Use when inputting a 4(0)-20mA
IV
CC
external reference signal to terminal
_
+
IV. P.PrG parameter #2 "priority of RR
terminal input" should be set to 0 "on".
See page 7-5.
Use when inputting 0-5Vdc external
IV
CC
reference signal to terminal IV. P.Prg
_
+
parameter #2 " priority of RR terminal
input" should be set to 0 "on".
See page 7-5.
Use when inputting 0-10Vdc external
IV
CC
reference signal to terminal RR.
_
P.Prg parameter #2 " priority of RR
terminal input" should be set to 1 "on".
See page 7-5.
0-10Vdc
Use when inputting 0-10Vdc external
IV
CC
reference signal to terminal RR.
_
P.Prg parameter #2 " priority of RR
terminal input" should be set to 1 "on".
See page 7-5.
Use when inputting a 4(0)-20mA
IV
CC
external reference signal to terminal IV
_
and a 0-10Vdc reference signal to
+
terminal RR. P.PrG parameter #2
"priority of RR terminal input" should be
set to 1 "on". Terminal RR will override
"have priority over" terminal IV when
0-20mA
switch (SW) is closed.
(4-20mA)
See page 7-5.
Function