Parameter Flow

This section describes the parameters set in each
level. Pressing the M key at the last parameter in
each level returns to the top parameter in that level.
Adjustment Level
P
at
AT Execute/Cancel
off
M
cmwt
Communications Writing
off
M
ct1
P
Heater Current 1 Value
Monitor
0.0
M
lcr1
P
Leakage Current 1
Monitor
0.0
M
hb1
P
Heater Burnout Detection 1
0.0
M
hs1
P
HS Alarm 1
50.0
M
sp-0
C
SP 0
0
M
sp-1
C
SP1
0
SP Used By
M
Multi-SP
sp-2
C
SP 2
0
M
sp-3
C
SP 3
0
M
ins
C
Temperature Input Shift
0.0
1-Point Shift
M
insh
C
Upper-Limit Temperature
Input Shift Value
0.0
M
2-Point Shift
insl
C
Lower-Limit Temperature
Input Shift Value
0.0
M
Press the O Key less than 1 s.
Press the O Key less than 1 s.
p
C
Proportional Band
8.0
M
i
P
Integral Time
233
PID Settings
M
d
P
Derivative Time
40
M
c-sc
P
Cooling Coefficient
1.00
Heating/Cooli
M
ng
c-db
C
Dead Band
0.0
M
of-r
P
Manual Reset Value
Clear the Offset During Stabil-
50.0
ization of P or PD Control.
M
hys
C
Hysteresis (Heating)
1.0
Hysteresis
M
Settings
chys
C
Hysteresis (Cooling)
1.0
M
sprt
C
SP Ramp Set Value
off
M
ol-h
P
MV Upper Limit
105.0
M
ol-l
P
MV Lower Limit
-5.0
M
Set either of these parameters.
Power ON
Starting in manual mode.
Manual control level
25
C
Press the
PID control
O Key for
only
at least 1 s
PV/MV
Operation Level
C
25
Process Value
Added When Additional
PV Display is ON.
M
25
C
Process value/
set point
0
M
Auto/Manual Switch
a-m
P
PID Control Only.
Added When Auto/Manual
Press the
O Key for
Select Addition is ON.
M
at least 3 s.
m-sp
P
Multi-SP
0
Set Point Setting
M
sp-m
C
Set Point During SP
Ramp
0
M
ct1
P
Heater Current 1
Value Monitor
0.0
M
lcr1
P
Leakage Current 1
Monitor
0.0
M
r-s
P
RUN/STOP
run
M
Press the O and M Keys for at
least 3 s. Display flashess.
Protect Level
The time taken to move to the protect level can be
adjusted by changing the "Move to protect level
time" setting.
Operation/Adjustment Protect
Restricts Displaying And
oapt
P
Modifying Menus In Operation,
Adjustment, And Manual
0
Control Levels.
M
Initial Setting/Communications
icpt
P
Protect
This Protect Level Restricts
1
Movement To The Initial Setting,
Communications Setting, And
M
Advanced Function Setting
Levels.
wtpt
P
Setting Change Protect
off
Protects Changes To Setups By
Operating The Front Panel Keys.
M
Appendix A
Press the O Key for at
least 3 s. Displays other than
that for switching between
automatic and manual.
Starting in automatic
mode.
C
al-1
Alarm Value 1
0
M
al1h
C
Alarm Value
Upper Limit 1
0
M
al1l
C
Alarm Value
Lower Limit 1
0
M
C
al-2
Alarm Value 2
0
M
al2h
C
Alarm Value
Upper Limit 2
0
M
C
al2l
Alarm Value
Lower Limit 2
0
M
al-3
C
Alarm Value 3
0
M
al3h
C
Alarm Value
Upper Limit 3
0
M
al3l
C
Alarm Value
Lower Limit 3
0
M
o
P
MV Monitor
(Heating)
0.0
M
c-o
P
MV Monitor
(Cooling)
0.0
M
Press the O Key
Press the O and
M
Keys
less than 1 s
for at least 1 s.
Communications Setting Level
Displayed only for models with communications.
Changes are effective after cycling power or
after a software reset.
psel
Protocol Setting
Switches Between CompoWay/F
cwf
(SYSWAY) And Modbus.
M
u-no
Communications Unit No.
1
M
bps
Communications Baud Rate
CompoWay/F
9.6
(SYSWAY) Only
M
len
Communications
Data Length
7
M
sbit
Communications Stop Bits
2
M
prty
Communications Parity
even
M
sdwt
Send Data Wait Time
20
M
175