Adjustment Level
hb1
Heater Burnout Detection 1
Function
Setting
See
See
hs1
HS Alarm 1
Function
Setting
See
See
110
This parameter sets the current for the heater burnout alarm to be output.
• The heater burnout alarm is output when the heater current value falls
below the setting of this parameter.
• When the set value is 0.0, the heater burnout alarm is turned OFF. When
the set value is 50.0, the heater burnout alarm will turn ON.
Setting range
Unit
0.0 to 50.0
A
Related Parameters
Heater current 1 value monitor (adjustment level): Page 109
HB ON/OFF: Page 135, Heater burnout latch, Heater burnout hysteresis:
Page 136 (advanced function setting level)
This parameter sets the current for the HS alarm to be output.
• The HS alarm is output when the leakage current value goes above the
setting of this parameter.
• When the set value is 50.0, the HS alarm is turned OFF. When the set
value is 0.0, the HS alarm will turn ON.
Setting range
Unit
0.0 to 50.0
A
Related Parameters
Leakage current 1 monitor (adjustment level): Page 109
HS alarm use, HS alarm latch: Page 143, HS alarm hysteresis: Page 144
(advanced function setting level): Page 143
Heater burnout and HS alarms must
be supported.
Alarm 1 must be assigned.
The "heater burnout detection"
parameter must be set to ON.
Default
0.0
Heater burnout and HS alarms must
be supported.
Alarm 1 must be assigned.
The "HS alarm" parameter must be
set to ON.
Default
50.0
Section 5-4