Venting - Harman Stove Company P61-2 Owner's Manual

Harman stove owners manual pellet stove p61-2
Table of Contents

Advertisement

Requirements for Terminating the Venting
WARNING: Venting terminals must not be re-
cessed into a wall or siding.
NOTE: Only PL vent pipe wall pass-throughs
and fire stops should be used when venting through
combustible materials.
NOTE: Always take into consideration the ef-
fect  the prevailing wind direction or other wind cur-
rents will cause with flyash and /or smoke when plac-
ing the termination.
In addition, the following must be observed:
A. The clearance above grade  must be a mini-
mum of 18".
1
B. The clearance to a window or door that may
be opened must be a minimum of 48".
( with outside air installed, 18î )
C. A  12"    clearance  to  a  permanently  closed
window  is  recommended to prevent condensation
on the window.
D. The vertical clearance to a ventilated soffit
located above the terminal within a horizontal dis-
tance of 2 feet (60 cm) from the center-line of the
terminal  must be a minimum of 18".
E. The clearance to an unventilated soffit  must
be a minimum of 12".
F.  The  clearance  to  an  outside  corner  is  11"
from center of pipe.
G. The clearance to an inside corner is 12".
H.  A vent must not be installed within 3 feet (90
cm)  above a meter/regulator assembly when mea-
sured from the horizontal center-line of the regula-
tor.
1
I. The clearance to service regulator vent outlet
must be a minimum of 6 feet.
V
= Vent terminal

Venting

1
1
Fixed
Closed
Openable
O p e n a b l e
A
= Air supply inlet
 6
J. The clearance to a non-mechanical air sup-
ply inlet to the building or the combustion air inlet to
any other appliance must be a minimum of 48î.
K.  The  clearance  to  a  mechanical  air  supply
inlet must be a minimum of 10 feet.
(with outside air installed, 6 feet )
L. The clearance above a paved sidewalk or a
paved driveway located on public property must be
a minimum of  7 feet.
1,2
M. The clearance under a veranda, porch, deck
 
or balcony must be a minimum of 12 inches.
NOTE:  The clearance to vegetation and other
exterior combustibles such as mulch is 36î as mea-
sured from the center of the outlet or cap. This 36î
radius  continues  to  grade  or  a  minimum  of  7  feet
below the outlet.
Certain Canadian and or  Local codes or regu-
1
lations may require different clearances.
A vent shall not terminate directly above a side-
2
walk or paved driveway which is located between
two single †family dwellings and serves both dwell-
ings.
3
Only permitted if veranda, porch, deck, or bal-
cony is fully open on a minimum of  2 sides beneath
the floor.
NOTE:  Where  passage  through  a  wall,  or
partition of combustible construction is desired,
the installation shall conform to CAN/CSA-B365.
(if in  Canada)
Inside  Corner
Detail
Fixed
Closed
= Area where terminal is not permitted
1
1
1,3