Mitsubishi Electric MSZ-D30 Installation Manual page 4

Split-type air conditioners
Hide thumbs Also See for MSZ-D30:

Advertisement

2-1. ATTACHING
THE INSTALLATION
PLATE
Find a stud in the wall to attach installation plate (1) horizontally on the wall with screws (2).
To prevent installation
plate (1) from vibrating, be sure to install the attachment
screws
in the holes indicated in the illustration.
For added support, additional
screws
may also
be installed in other holes.
If the recessed bolt is too long, change it for a shorter one (field-supplied).
2=2. DRILLING
t) Determine where the holes will be located on the wall.
2) Drill a _ 3 in. (75 ram) hole. The outdoor
side should be 6/32 to 9/32 in. (5 to 7 mm)
lower than the indoor side.
3) Insert wall hole sleeve (C).
2-3. CONNECTING
WIRES
FOR INDOOR
UNIT
Note:
When the indoor unit is powered from the outdoor unit, depending
on local code, a discon-
nect switch needs to be installed to a power supply circuit.
t) Open the front panel.
2) Place the upper part of the indoor unit on the installation
plate.
3) Remove electrical
cover.
4) Remove VA clamp.
5) Remove corner box.
6) Remove cable guide.
7) Remove conduit plate.
8) Attach conduit pipe (for rear piping) / elbow joint (for right, left, or downward
piping) to
conduit plate with lock nut. The thread of the installed conduit pipe / elbow joint appear-
ing inside should be less than 3/8 in. (10 mm). (Fig. 1) Elbow joint should appear less
than 1-3/16 in. (30 mm) outside. (Fig. 2)
9) Process the end of ground wire (Fig. 3). Connect it to the ground
terminal of electrical
parts box.
10) Process
the end of indoor/outdoor
unit connecting
wire (A) (Fig.3). Attach
it to the
terminal block. Be careful not to make mis-wiring.
Attach the wire to the terminal
block
securely so that its core cannot be seen, and no external force affects the connecting
section of the terminal block.
11) Firmly tighten the terminal screws. After tightening,
verify that the wires are tightly fas-
tened.
12) Reinstall conduit plate.
t3) Reinstall cable guide.
14) According
to the piping direction,
remove the shaded
part of the left side of box (Fig.4)
or corner box (Fig. 5).
15) Reinstall VA clamp.
t6) Reinstall electrical cover.
17) Reinstall panel assembly.
---.- ....
_/
2-13/16 in. (70 ram) or more
Celhng
5-1/8 in (130 ram) or more for left
_'_////////////////////////////////_//
.......
_'_/'_/,_ and leftback piping (using sp.... )
lnstaflation plate (1)
/'_
_e
/
/'_
Le,e,
_/_// ....
I<
_
--_ ...... ....
_4 in.
8 11/16in
_/_
4-11/16in
_
o_D -_
..
_ (100 mm)_
......
_//
(
)
_
o ..........................
':L ...............................................
_
or more
,,
Attachme_
__
_!ei_:
f
hole
* Same for left hole,
Waft
o3in.
(7 5 r'nr'n)--L_/_
(E5/372rg_r3_ in
Outdoor side
Electrical
cover
ate terminals
• Forfuture
servicing, leave some
slack in the connecting wires.
Elbow joint
Remark:
INDOOR UNIT
* A disconnect switch is required,
r
_
Grounding
Check the local code.
/Terminal block Jj
terminal**
** Use a ring tongue terminal in
i
m ( ,
order to connect a ground wire
I
51__.
to terminal.
Disconnect
_,_
switch*
208/230 V AC
1phase, 60 Hz\
OUTDOOR UNIT
, '
r;A:]
_ o
!
L_:
: ?"
Ground
Grounding terminal**
Power supply
208/230 V AC,
1 phase 2 wires,
60 Hz
Conduit plate
Less than 3/8 in,
(10 ram)
Lock nut
--
Conduit pipe or
elbow joint
5/8 in.
2-3/16in.
_
(15mm)
(55 ram)
[[
Fig. 1
f
Lead _
wire
Make
ground
wire
a little
longer
than
others.
(More
than
1-9/16
in. [40 mm])
Fig. 3
Corner box
Remove panel for
Remove panel
piping on bottom
for piping on right
side of unit
side of unit
Fig. 5
Condut_plate
_,
_
[
Less than 1-3/16 in.
(30 ram)
_
Elbow joint
(for right, left, or downward
piping)
Fig. 2
_Box
Remove panel
/
for piping on
Remove panel for piping
left side of unit on bottom left side of unit
Fig. 4