Fuel Consumption
See Figure 7 for fuel supply requirements
at half and full
load for both natural gas and LP vapor.
Model
Natural Gas*
I/2
Full
Load
Load
1938-0
84
162
34.19
1815-0
102
195
41.03
* = Natural Gas is in cubic feet per hour
** = LPVapor is in cubic feet per hour
LP Vapor **
I/2 Load
Full Load
65.8 I
78.63
Fuel Pipe Sizing
Figures 8 and 9 provide the maximum capacity of pipe in
cubic feet of gas per hour for gas pressures of 0.5 psi or
less and a pressure drop of 0.3 in. water column. Specific
gravity of gas is shown.
Listed values compensate
for a nominal amount of
restriction
from bends, fittings, etc. If an unusual number of
fittings, bends, or other restrictions
are used, please refer
to federal and local codes.
I Oft
Y2"
168
¾"
346
I"
653
Natural Gas (sg=0.65)
15E
40E
146
115
93
79
293
240
192
163
549
446
360
307
50ft
80_
70
63
59
55
145
132
120
113
274
250
230
211
90_
51
48
106
99
197
187
NPT
10_
15_
½"
II0
96
¾"
277
192
I"
428
360
Liquefied Petroleum
(LP)(sg=l.50)
20_
30_
40_
50_
60_
70_
80_
90_
100k
76
61
52
46
42
38
36
33
32
158
126
107
95
87
79
74
69
65
293
236
202
180
164
151
139
129
123